To: Honorable Mayor and City Council
From: Bridger Morrison
Date: March 23, 2026
Re: Adoption of City Construction Standards
Public Works Department
290 E. Linden Avenue, Chubbuck, ID 83202
208.237.2430 — Fax 208.237.2409
www.CityofChubbuck.us
Over the last several years, the Public Works Department has been working to develop a comprehensive
construction standards document. For a very long time, the City has had the Idaho Standards for Public
Works Construction (ISPWC) as the City's adopted construction standards. That is not changing. That
document was created such that it could be used by all cities in the state. However, it is intended that
each city make adjustments to fit their specific needs. Over the years, Chubbuck has developed those
preferences and specific requirements that might be unique to Chubbuck. The challenge has been that
many of those Chubbuck-specific standards and requirements have existed in a variety of formats and
documents. Some are notes and drawings that the City requires to be added to construction plans.
Some are documents that have been provided to parts and material suppliers, while others have been
included in design manuals and ordinances. Keeping all of that straight has been a challenge for
developers, designers, contractors, and even our own staff.
The attached document, titled "Development and Project Design Standards and Revisions to the Idaho
Standards for Public Works Construction, Current Edition," is the result of this dedicated effort to
compile all of that historical information into a single document. In addition, we identified some areas
where additional improvements are needed. This includes problems that have arisen in the past or new
methods or technology that will provide a better product for the city and reduce future maintenance
efforts and costs. We also reviewed the City of Pocatello's construction standards to identify areas
where we can add consistency for Contractors who may work in both cities.
For the most part, these standards are familiar to designers and contractors. There are a few new things
we've added to get a better product and reduce future maintenance costs and challenges, but we do
not believe there is anything substantial in these standards that will affect the end cost of construction.
All of the standards have been developed with the goal of balancing the long-term performance of our
infrastructure and the maintenance costs of the city with the initial cost of construction.
I understand that the format of these construction standards is a little strange and may not be fully
understood without reviewing the ISPWC at the same time. If you have any questions about specific
sections of these standards, our public works staff would be happy to review the ISPWC and the
standards with you.
C:�Users Vbowers�AppData�Local �Microsoft �Windows �lNetCache�Content. Outlook�98L01ABQ�Recommendation for Standards
Adoption -Council BM 03.21.2026.docx
I am requesting the opportunity to review these recommended construction standards with you at the
upcoming Council Meeting and am asking you to consider adopting these construction standards. Please
reach out if you have any questions you would like to discuss prior to the meeting. If not, I look forward
to the discussion on April V
Sincerely,
Bridger Morrison, P.E.
Public Works Director/City Engineer
CHUBBUCK
1 0 R H 0
290 E. Linden Avenue, Chubbuck, ID 83202
208.237.2430 — Fax 208.237.2409
www.CityofChubbuck.us
zaa�,
CHUBBUCK
1 0 A H O
CITY OF CHUBBUCK
Development and Project Design Standards
FM
Revisions to the Idaho Standards for Public Works
Construction
Current Edition
April 2026
This Page Left Intentionally Blank
Table of Contents
Introduction........................................................
Design Requirements and General Information
Construction Standards .......................................
1
2
3
Division300 —Trenching ...................................................................................................................... 3
Section 301— Trench Excavation: ..................................................................................................... 3
Section305 — Pipe Bedding: ............................................................................................................. 3
Section 306 —Trench Backfill: .......................................................................................................... 3
Section 307 — Street Cuts and Surface Repairs: ............................................................................... 4
City of Chubbuck Standard Drawings................................................................................................5
CSD -301— Typical Trench.......................................................................................................... 6
CSD -302 — Flowable Fill Utility Crossing...................................................................................7
Division400 — Potable Water...............................................................................................................8
General Information:
DistributionPipe: ...................................................................................................................... 8
MainlineValve: .........................................................................................................................
9
FireHydrant: ...........................................................................................................................
10
ServiceLine: .............................................................................................................................
10
Section 401— Water Pipe and Fittings: ..........................................................................................
11
Section 402 — Hydraulic Valves: .....................................................................................................17
Section403 — Hydrants: .................................................................................................................19
Section 404 — Water Service Line and Meters: ..............................................................................
19
City of Chubbuck Standard Drawings..............................................................................................22
CSD -401-1" Potable Water Service......................................................................................
23
CSD -402 — 2" Potable Water Service......................................................................................
26
CSD -403 — 3" to 12" Potable Water Service...........................................................................
29
CSD -404
— Fire Hydrant ......
CSD -405
— Valve Box and Lid
CSD -406
— Flush Hydrant ....
32
34
35
Division500 — Sanitary Sewer............................................................................................................
36
General Information:
SanitarySewer Pipe: ...............................................................................................................
36
SanitarySewer Manhole: .......................................................................................................37
SewerService Line: .................................................................................................................
37
Section 501— Gravity Sewers: ........................................................................................................
38
Section502 — Manholes: ................................................................................................................
38
Section 504 — Sewer Services: ........................................................................................................
39
Division700 — Concrete...................................................................................................................... 41
General Information:
ConcreteMix: .........................................................................................................................41
Section 703 — Cast -In -Place Concrete: ...........................................................................................41
Section 706 — Other Concrete Construction: ................................................................................. 42
City of Chubbuck Standard Drawings..............................................................................................43
CSD -701— Concrete Ribbon Curb...........................................................................................44
CSD -702 — Concrete Scupper..................................................................................................45
CSD -703 — Commercial Approach...........................................................................................47
Division 800 — Aggregates and Asphalt.............................................................................................48
General Information:
AsphaltMix: ............................................................................................................................ 48
Section 810— Plant Mix Pavement: ................................................................................................ 48
Division 900 — Pressure Irrigation......................................................................................................50
General Information:
Requirement: .......................................................................................................................... 50
Pressure Irrigation Pipe: ......................................................................................................... 50
Pressure Irrigation Valve: .......................................................................................................51
PressureIrrigation Drian:.......................................................................................................52
Pressure Irrigation Service: ..................................................................................................... 52
Backflow Prevention Device: .................................................................................................. 53
Section 901— Pressure Irrigation Pipe and Fittings: ...................................................................... 53
Section 902 — Pressure Irrigation Valves: ....................................................................................... 56
Section 903 — Pressure Irrigation Service Lines and Appurtenances: ............................................. 58
City of Chubbuck Standard Drawings..............................................................................................61
CSD -901-1" Pressure Irrigation Service................................................................................ 62
CSD -902 — Pressure Irrigation Drain....................................................................................... 64
CSD -903 —1" Backflow Prevention Device............................................................................. 66
Division 1100 —Traffic .....................................
Section 1102 — Street Lighting: ...................
Section 1105 — Permanent Traffic Signing: .
City of Chubbuck Standard Drawings...........
CSD -1101— Street Light Installation.....
CSD -1102 — Street Name Sign ..............
68
68
69
70
71
72
Division2000 — Miscellaneous........................................................................................................... 73
Section 2060 — Neighborhood Mailbox: ......................................................................................... 73
Section 2070 — Garbage Dumpster Enclosure: ............................................................................... 74
City of Chubbuck Standard Drawings..............................................................................................76
CSD -2001— Neighborhood Mailbox....................................................................................... 77
CSD -2002 —Garbage Dumpster Enclosure
CSD -2003 — Sanitation Truck Turnaround
Division 2100 — QC Division
Supplement Field QC Manual
79
80
81
81
Introduction
The purpose of this document is to provide additional design requirements for developments and
projects in the City of Chubbuck. In addition, this document modifies the latest edition of Idaho
Standard for Public Works Construction (ISPWC). The ISPWC and these modifications, referred to as
the City of Chubbuck Revisions to the ISPWC, are to be used as the City's standards and
specifications for construction of public improvements within the City of Chubbuck. In the event of
a conflict between ISPWC and City of Chubbuck Revisions to the ISPWC, the City of Chubbuck
Revisions shall govern unless the contrary is approved in writing by City of Chubbuck City Engineer
for a specific circumstance. The terms "Engineer" and "City' in the latest edition of ISPWC and City
of Chubbuck Revisions, shall refer to the City of Chubbuck City Engineer.
Design Requirements and General Information
In addition to construction standards, the following information includes limited design
requirements and clarifications, along with other general information related to the design and
construction of development projects and other improvement projects. This is not a complete
design guide as the city ordinances and other adopted design guides and policies contain the
majority of the City's design requirements. The following information is intended to supplement
and clarify some of those other requirements.
Construction Standards
The current edition of the Idaho Standards for Public Works Construction (ISPWC) has been
adopted as the City's construction standards. The following revisions supplement or modify the
current edition of the ISPWC and apply where the City's construction standards apply.
Amend the ISPWC as follows:
Division 300 —Trenching
Section 301— Trench Excavation:
Replace Section 3.1.A with the followi
3.1— General Requirements:
A. Excavate, as necessary, at the locations indicated in the Contract Documents and staked in
the field for the installation of pipelines, services, utilities, and ancillary items. Excavate
trenches per City of Chubbuck Standard Drawings CSD -301 (Typical Trench) or CSD -302
(Flowable Fill Utility Crossing), or ISPWC Standard Drawing SD -306 (Utility Trench).
Section 305 — Pipe Bedding:
Add Section 2.7 as follows:
2.7 — Type V Bedding
A. Acceptable bedding material for pressure water pipe also includes sand with 100% passing
the 1/2 -inch sieve, 80% or more passing the No. 4 Sieve, and less than 6% passing the
No.200 Sieve.
B. Compact Type V bedding in accordance with ISPWC Section 3.10.
Section 306 —Trench Backfill:
Replace Section 3.1.E with the followi
3.1—General Requirements:
E. Backfill per City of Chubbuck Standard Drawing CSD -301 (Typical Trench).
Section 307 — Street Cuts and Surface Repairs
Add Section 3.14 as follows:
3.14— Mastic Sealant
A. Hot applied, pourable, aggregate filled, polymer modified asphalt pavement repair mastic
(Mastic Sealant), shall be used where required by the City. Product to be approved by the
City prior to use.
B. Installation of Mastic Sealant in the public right-of-way, shall be installed from March 1 to
October 31 and when the temperature requirements as specified by the manufacturer are
met. An exception may be allowed with written approval from City Engineer.
4
Division 300 — Trenching
City of Chubbuck Standard Drawings
CSD -301 Typical Trench
CSD -302 Flowable Fill Utility Crossing
RADE OR
NATO �l I SP OIL
NATURAL GROUND FINISH GRADE 1
U 1 O 01
0 1 12 1
1111- l
uJ
<nz�
www
Q�o
LU
N
U)U)
ww
Fy o-
Qn
6" MIN.
SEE NOTE B
12" MIN
EACH SIDE
OUTSIDE DIA. OF
PIPE PLUS 2'-0"
A. TRENCH EXCAVATION PER
SECTION -301 OF ISPWC
B. PIPE BEDDING MATERIAL 4" BELOW
THE BOTTOM OF THE PIPE, 6" FOR
PIPES 30 INCHES AND LARGER.
C. BACKFILL AND COMPACTION PER
SECTION -306 OF ISPWC
FOR PUBLIC
WORKS
CHUBBUCK CONSTRUCTION
STANDARDS
1 9 A H 0
18" MIN.
MATERIAL LIST:
1. LOCAL CUT BACK, 12" MIN BOTH SIDES
TYPICAL
2. SURFACE REPAIR WIDTH
3. EXISTING SURFACE
4. EXISTING BASE
5. TRENCH BACK SLOPE PER O.S.H.A. OR
SUITABLE SHORING
6. TRENCH BACKFILL PER SECTION -306
OF ISPWC
7. VERTICAL TRENCH WALLS SHORING
PER O.S.H.A.
8. TYPE I PIPE BEDDING PER
SECTION -305 OF ISPWC
9. FOUNDATION STABILIZATION MAY
VARY PER SOIL TYPE AND STABILITY
(PER SECTION -304 OF ISPWC)
10. UNDISTURBED SOIL (TYP)
11. SURFACE REPAIR AND BASE PER
SECTION -307 OF ISPWC
12. UPPER COMPACTION ZONE
13. LOWER COMPACTION ZONE
14. 6" WIDE METALLIC WARNING TAPE,
POLYETHYLENE VINYL, COLOR AND
LABELED ACCORDINGLY TO TYPE OF
PIPE INSTALLATION (SEE MATERIAL
SPECIFICATIONS)
LAST REVISED 3/24/2026
STANDARD DRAWING NO:
TYPICAL TRENCH CSD -301 1 OF 1
D
(D C�
z
13 14
<O
18"-24"
0
sLo
7
12" MIN
EACH SIDE
OUTSIDE DIA. OF
PIPE PLUS 2'-0"
A. TRENCH EXCAVATION PER
SECTION -301 OF ISPWC
B. PIPE BEDDING MATERIAL 4" BELOW
THE BOTTOM OF THE PIPE, 6" FOR
PIPES 30 INCHES AND LARGER.
C. BACKFILL AND COMPACTION PER
SECTION -306 OF ISPWC
FOR PUBLIC
WORKS
CHUBBUCK CONSTRUCTION
STANDARDS
1 9 A H 0
18" MIN.
MATERIAL LIST:
1. LOCAL CUT BACK, 12" MIN BOTH SIDES
TYPICAL
2. SURFACE REPAIR WIDTH
3. EXISTING SURFACE
4. EXISTING BASE
5. TRENCH BACK SLOPE PER O.S.H.A. OR
SUITABLE SHORING
6. TRENCH BACKFILL PER SECTION -306
OF ISPWC
7. VERTICAL TRENCH WALLS SHORING
PER O.S.H.A.
8. TYPE I PIPE BEDDING PER
SECTION -305 OF ISPWC
9. FOUNDATION STABILIZATION MAY
VARY PER SOIL TYPE AND STABILITY
(PER SECTION -304 OF ISPWC)
10. UNDISTURBED SOIL (TYP)
11. SURFACE REPAIR AND BASE PER
SECTION -307 OF ISPWC
12. UPPER COMPACTION ZONE
13. LOWER COMPACTION ZONE
14. 6" WIDE METALLIC WARNING TAPE,
POLYETHYLENE VINYL, COLOR AND
LABELED ACCORDINGLY TO TYPE OF
PIPE INSTALLATION (SEE MATERIAL
SPECIFICATIONS)
LAST REVISED 3/24/2026
STANDARD DRAWING NO:
TYPICAL TRENCH CSD -301 1 OF 1
8" MAX FOR COLD MIX
ASPHALT REPAIR
ry
CHUBBUCK
IDDH0
FOR PUBLIC
WORKS
CONSTRUCTION
STANDARDS
4DE
TING ASHPALT
MATERIAL LIST:
1. COLD MIX ASPHALT COULD BE USED FOR
POTHOLES THAT DO NOT EXCEED EIGHT
INCHES (8") IN DIAMETER. THICKNESS
SHALL BE 3/8" GREATER THAN EXISTING
ASPHALT AND SHALL PROTRUDE ABOVE
FINISH GRADE.
2. FLOWABLE FILL 300 PSI AS PER
SECTION -703 OF ISPWC
3. 3/4" MINUS CRUSHED AGGREGATE OR
SAND BEDDING
4. PIPE OR CONDUIT
A I f -%T r C+ .
A. USE THIS DETAIL FOR POTHOLES OVER
ALL UTILITIES.
B. SAWCUT ALL ASPHALT IN NEAT LINES.
LAST REVISED 3/24/2026
FLOWABLE FILL STANDARD DRAWING NO:
UTILITY CROSSING I CSD -302 1 OF 1
Division 400 — Potable Water
General Information:
Distribution Pipe:
A. All such distribution pipe extensions and installations shall be in dedicated public right of
way areas and shall extend the full length of the frontage of the property being served. All
distribution pipe extensions/installations shall conform in all respects to the standards,
specifications, and material requirements set forth in these standards and the ISPWC.
B. Sizing:
Distribution pipe shall be minimum of eight inches (8") nominal diameter and may require
to be upsized in areas such as near arterial and collector streets, in accordance with the
current Water System Facility Planning Study or Master Plan.
In areas with new development, the City of Chubbuck may require a hydraulic analysis to
verify adequate system pressure and flows. If a proposed water system will be a part of a
larger phased development, it is required that the larger development be considered in the
hydraulic evaluation. A hydraulic analysis that includes a larger development may be
satisfactory to meet the hydraulic analysis requirement for a multi -phase development.
Hydraulic model boundary conditions including water supply and flow controls shall be
clearly defined. Summary of design criteria used, including water demands, peaking factors,
pipe roughness, etc. shall be included.
The distribution system shall be designed so that it will provide a minimum fire flow of one
thousand five hundred (1,500) gallons per minute in addition to system domestic
demands. Additional fire flow demands may be required in industrial and commercial
areas.
C. Dead End:
Dead end distribution pipe shall be avoided whenever possible and should not exceed
eight hundred (800) feet in length. Each dead-end distribution pipe shall have a hydrant, or
a flushing device installed at its termination. Two-inch flush hydrants rather than a fire
hydrant are not desirable but may be warranted under special circumstances, as
determined by City Engineer.
N
D. Inside Easements:
The City of Chubbuck may require or allow water mains to be installed in utility easements if
it is deemed necessary for the good of the water delivery system.
Depending upon site specific conditions, distribution pipe located in an easement outside of
road right-of-way may be required to be fused HDPE pipe as determined by the City
Engineer.
Access to all water structures shall be provided by easements of no less than twenty feet
(20') in width, centered over the water structure to maintain ten feet (10') minimum from
the easement sideline. Greater easement width may be required in special circumstances.
E. Pipe Cover:
The top of pipe to finish grade for all distribution pipe and service lines shall be a maximum
of six feet (6') and minimum of five feet (5'). In some special cases, with the approval of
the City Engineer, the distribution pipe may be installed deeper below other utilities or in
areas where air entrapment might otherwise occur, given the extents of the pipe greater
than six feet (6') deep is minimized.
F. Mainline Coupling:
Mainline couplings should be used to a minimum and only following approval of the City
Engineer or Water Superintendent.
G. Utility Separation:
Distribution Pipe shall be no closer than five feet (5') feet horizontal separation and no
closer than twelve inches (12") of vertical separation from any other utility. All non -potable
water line separation requirements apply.
Mainline Valve:
A. All mainline valves and fittings located near other fittings shall be required to be flanged.
B. Location:
Valves shall be installed on all directions of the distribution pipe including all crosses or
tees unless otherwise approved by the City.
0
C. Spacing:
The maximum distance between valves shall be five hundred feet (500') in commercial
districts and eight hundred feet (800') in other districts as measured following the
distribution pipe.
D. At all high points in the water main where air entrapment is likely to occur, combination air
release / air vacuum valves shall be required. Valve sizing calculations will need to be
provided by the design engineer, and the size and model indicated on construction plans.
Adequate space shall be provided inside a standard manhole to allow for easy access and
maintenance. The size and height of all fittings shall be verified.
Fire Hydrant:
A. Location:
Fire hydrants shall be located at the street intersection or at the lot line between adjacent
properties, behind the street right of way in the utility easement with the bottom flange
located not less than 2 inches and not greater than 8 inches above finished grade.
B. Spacing:
No lot frontage shall be located more than two hundred fifty feet (250') from a fire hydrant
as measured in the street right of way.
Service Line:
A. Sizing:
Water service lines shall be sized in accordance with requirements of the latest edition of
the Idaho plumbing code adopted by the city, but shall not be smaller than one inch (1")
nominal size. Applicants for commercial developments requiring water service in excess of
one inch (1") shall be required to submit, pursuant to their application, and as directed by
the public works director, the fixture count for the structure, or their normal and
maximum intermittent flow rates to department staff to establish the size of meter
required, regardless of the inlet and outlet pipe size.
Upsizing the service line beyond the meter box may be allowed at the expense of the
property owner. The connection shall be outside the meter box on the property owner's
side of the service line.
B. Installation:
All service installations connected to the water system that have been or will be
abandoned or that have not been used for three (3) years or that for any reason have
10
become useless for further service, shall be disconnected at the main by the property
owner or the City of Chubbuck - Public Works Department, at the property owner's
expense, and all pipe and appurtenances removed shall be the property of the City of
Chubbuck. Exceptions may be granted by the Chubbuck Public Works Department for
special circumstances, including recent installations awaiting building construction.
C. Separate Lines Required:
Each premises for which title may be transferred, whether connected to another structure
under one roof, or standing separately on a single parcel of land shall be required to have
its own separate water service line, except condominium associations under separate
agreement with the City of Chubbuck.
Each water service shall have an individual meter box, separated from any other water
service.
D. Maintenance:
The City of Chubbuck owns and the Public Works Department shall maintain all completed
service lines after installation from the point of connection at the water main through the
meter vault to the outside edge of the meter vault in cases where the meter vault is set at
the nearest property line abutting the main, or to the nearest property line abutting the
main in cases where the meter vault or metering equipment is situated in a building or
otherwise not adjacent to the nearest property line abutting the main.
E. Repairs:
If repairs or replacement of any water service line is rendered necessary by the act,
neglect, or carelessness of the owner or occupant of the premises, any expense incurred
thereby by the City of Chubbuck shall be charged against and collected from the owner or
occupant.
Section 401— Water Pipe and Fittings:
Replace Sections 2.2.A and 2.2.13 with the followi
2.2 — Polyvinyl Chloride (PVC) Pipe and Fittings:
A. PVC Pressure Pipe Sizes 4 inch through 36 inch for Water Distribution:
ANSI/AWWA C 900-16
Pressure Class: Minimum DR -18
2. Outside Diameter Basis: Cast Iron (CI) pipe equivalent
3. Joints: Bell and spigot end with ASTM F 477 elastomeric gaskets
4. Color: Blue
Remove Section 2.2.C.3 in its entire
11
Replace Section 2.9.0 with the following:
2.9 — Mechanical Restraint:
C. Application: Approved for above -grade installation. All mechanical joint fittings below grade
shall be mechanically restrained using mechanical restraints meeting the requirements of
ISPWC Section 401.2.9. Mechanical restraints shall be in addition to thrust blocks.
Add Section 2.9.D as follows:
D. As an alternative to installing mechanical restraints on fittings, an Alpha Restrained Joint
Fitting manufactured by American Flow Control will be allowed where prior approval by the
City is provided.
Replace Section 2.10 with the following:
2.10 — Locate Wire:
A. Type: (No 12 AWG) single strand 12 -gauge copper clad steel (CCS) wire with blue high-
density polyethylene (HDPE) insulated jacket coating for direct bury.
B. Splicing: 3M DBR direct bury splice kit or City approved equivalent and shall be watertight
to provide electrical continuity.
C. Locate Wire Access Point: Snakepit tracer box style CD14*TP with blue locking cover
located behind the fire hydrant in accordance with City of Chubbuck Standard Drawing
CSD -404 (Fire Hydrant).
Add Section 2.13 and 2.14 as follows:
2.13 — Warning Tape:
A. Type: 6" wide metallic warning tape, blue polyethylene vinyl labelled "POTABLE WATER".
2.14 — Mainline Tapping Saddle:
A. Tapping saddle shall conform to AWWA C223.
B. Pressure Class: Minimum 175 psi
C. Connection: Flange
D. Manufacture and Model: Romac SST, Mueller H304, or Ford FAST
Replace Section 3.2.0 with the followi
3.2 — Pipe Installation:
O. Locate wire shall be secured with suitable tape every 8 to 10 feet along the buried
distribution pipe.
12
Add Sections 3.2.R and 3.2.S as follows:
R. Install 6" wide metallic warning tape, blue polyethylene vinyl labelled "POTABLE WATER"
shall be placed between 18 to 24 inches above the distribution pipe.
S. Where fittings are located adjacent to other fittings, all fittings shall have flanged
connections between fittings.
Add Section 3.4.G as follows:
G. In addition to thrust blocks, all valves and fittings shall be restrained to the pipe with the use
of mechanical restraints per Section 2.9.
Replace Section 3.7 with the followi
3.7 — Locate Wire:
A. Locate wire shall be secured with suitable tape every 8 to 10 feet along the buried
distribution pipe. The locate wire shall interconnect to the locate wire of each service line
and hydrant lateral with 3M DBR direct bury splice kit or City approved equivalent and
shall be watertight to provide electrical continuity.
B. Locate wire shall be tested for continuity prior to road subgrade preparation. Any wire
found not to be continuous after testing shall be repaired or replaced to City satisfaction
by the contractor prior to roadway construction.
Replace Sections 3.9.A and 3.9.13 with the following:
3.9 — Flushing and Disinfection:
A. Flushing and Prior to Disinfection:
1. The water infrastructure shall be fully constructed prior to scheduling the City to witness
the pressure test, chlorination, or to take bacteriological (Bac-T) test. This shall include
all water mains, fittings and thrust blocks, hydrants, services, and all components in the
meter pit/box.
2. A minimum of five (5) business days prior to disinfection, the contractor shall submit to
the City, for approval, the chlorination plan. This plan shall include the locations of
chlorine injection points, flow direction, sample locations, and drainage areas. In certain
looped water systems, valves shall be labeled on the chlorination plan as open or closed
to direct the heavy chlorine mixture solution fully through the new water infrastructure.
This plan shall include all actions required to chlorinate the entirety of the new potable
water mains, hydrant laterals, and service lines.
3. Before the main is chlorinated, Contractor shall perform a preliminary flush of the line
by filling all lines with potable water and removing all air pockets, then thoroughly
flushing the main to scour and to remove contaminates or debris that may have been
introduced during construction. The City shall be onsite to operate the valve(s) that
13
feeds the potable water into the newly installed main, and to witness the preliminary
flush. The contractor shall provide enough drainage area and storage volume to meet
the minimum flushing velocity of 3.0 feet/second following AWWA C651-23, with two to
three volumes of the new water infrastructure, until the flush water is free of debris and
visibly clear. It is prohibited to discharge the flush water into any sanitary sewer or
storm drain infrastructure.
4. Table 1 shows the rates of flow required to produce a velocity of 3.0 feet/second in
various size pipes.
Table 1 Required flow and openings to flush pipelines
40 psi residual pressure in water main*
Pipe Diameter
Flow Required to Produce
3.0 ft/s (approx.)
Velocity in Main
Size of Tap Used,
in. (mm)
Number of Hydrants
Outlets
in.
(mm)
gpm (L/s)
1-1/2
1 (25) (38) 2 (51)
2-1/2 in. 4-1/2 in.
(64 mm) (114 mm)
4
(100)
120 (7.4)
1 - -
1 1
6
(150)
260 (16.7)
- 1 -
1 1
8
(200)
470 (29.7)
- 2 -
1 1
10
(250)
730 (46.3)
- 3 2
1 1
12
(300)
1,060 (66.7)
- - 3
2 1
16
(400)
1,880 (118.6)
- - 5
2 1
*With a 40 -psi (276 -kPa) pressure in the main with the hydrant flowing to atmosphere, a 2-1/2 in (64 -mm) hydrant outlet will
discharge approximately 1,000 gpm (63.1 L/s) and a 4-1/2" (114 -mm) hydrant outlet will discharge approximately 2,500 gpm
(160 L/s).
*Number of taps on pipe based on 3.0 ft/s discharge through 5 ft (1.5 m) of galvanized iron pipe with one 90° elbow.
B. Disinfection of Water Pipe:
1. General:
a. Comply with ANSI/AWWA C 651-23, Disinfecting Water Mains, these specifications,
and Engineer's direction.
b. The contractor shall provide 48-hour minimum advance notice to allow the City to
operate any necessary feeding valve(s), observe flushing, or to take the Bac-T test.
Valves that are utilized to flush or direct potable water or chlorine mixture solution
shall be readily accessible to the City.
14
d. During the chlorination process, the City shall be present to verify the water main,
service lines, and hydrant laterals are fully disinfected. The City will routinely check
the chlorine residual to ensure it is potent enough to thoroughly disinfect the pipe.
e. The contractor shall be responsible for flushing the line and for any impact caused
by the water. The City shall operate all valves for the flushing operation following
the contractor's direction.
2. Forms of Chlorine used to be pre -approved by the Engineer:
a. Liquid chlorine (gas) usually packaged in large steel containers is not allowed to be
used.
b. Acceptable form of chlorine is sodium hypochlorite in liquid form containing
approximately 5 to 15% available chlorine per ANSI / AWWA B300.
c. Calcium hypochlorite in the form of tablets or granules is not allowed to be used.
Replace Section 3.9.B.3.a with the following:
3. Methods of Chlorination used to be pre -approved by the Engineer:
a. Tablet or Granule Method Not Allowed
Replace Section 3.9.B.3.b.4 as follows:
b. Continuous Feed Method:
4. Critical points to inject chlorine shall be as close as possible to the source of
water, beginning at the new water main. Injection could be through a hydrant or
meter setter if within (10') ten feet from the source of water. If not attainable, a
chlorination injection tap will be required at the Contractor's expense. The
injection tap shall be installed within (10') ten feet of the source water. Once the
City has acceptable water quality results, the chlorination injection tap shall be
replaced with a threaded brass plug, to be witnessed by the City to verify that no
leaks occur. The flow shall be at a constant rate with the City routinely checking
the chlorine residual is potent enough to thoroughly disinfect the pipe. The flow
shall be continued until the end of each branch has constant levels of heavily
chlorinated water. The chlorine mixture shall remain in the newly installed water
infrastructure for 24 hours minimum prior to the final flush.
Replace Section 3.9.B.3.c with the following:
c. Slug Method:
1. Slug Method Not Allowed
15
Replace Section 3.9.0 with the following:
C. Final Flushing:
Upon removal of heavily chlorinated water, the Contractor shall use a dechlorinating
diffuser or device to reduce the chlorinated waste discharge. The City shall be present,
verifying chlorine residual levels are thoroughly neutralized, minimizing contamination
to the environment.
2. After the removal of the heavily chlorinated water, and prior to the first bacteriological
(Bac-T) test, with the City onsite operating the valve(s) that feeds the potable water into
the newly installed main, the contractor shall perform the final flush from the main,
valves, and branches right before the City takes the first Bac-T test.
Replace Section 3.9.D as follows:
D. Bacteriological Tests:
Bacteriological (Bac-T) test shall be collected from each 600 feet of the newly installed
water main with one (1) sample taken from each main branch. Samples are typically
taken from a fire hydrant, at or near the dead end of the new water main.
2. The bacteriological (Bac-T) testing shall be performed by the City, scheduled by the
contractor. The contractor shall coordinate with the City, to take two (2) Bac-T tests
back-to-back, 24 hours from each other. The timing shall be planned such that the
results do not come back from the laboratory on a weekend or holiday. Samples are
only collected on Monday thru Thursday, between 7:30 am to 4:30 pm, excluding
Holidays. Samples will NOT be collected on Fridays, Saturdays, Sundays, Holidays or the
day preceding a Holiday (if such holiday falls during the week). Under special approval
from the Water Superintendent, if a sample absolutely needs to be collected outside of
the approved dates and times, the contractor will be charged all extra costs associated
with the sampling and laboratory costs.
If results come back positive with unacceptable water quality, the water infrastructure
shall be disinfected and flushed again following the complete process above. The Contractor
shall be responsible for the testing costs required due to failing tests.
Add Section 3.12 as follows:
3.12 — Mainline Tapping:
A. For live taps onto a charged portion of the city's potable water system, all materials shall
be provided and installed by the contractor or customer. For taps of 12" or less in size, the
tapping will be performed by City staff. In no case shall a non -City of Chubbuck personnel
operate any part of the City's water system without prior written authorization of the City
of Chubbuck - Water Superintendent.
16
When a new mainline tap is required, the contractor shall excavate around the existing
main and the trench shall be sufficient to allow the City's tapping crew enough space at
each location to safely make the tap without any additional excavation. The adequacy and
safety of the excavation shall be at the sole discretion of the City's tapping crew. If the
City's tapping crew determines that any excavation does not meet City standards, the crew
shall have the option to refuse to make the tap and will reschedule at least 2 days hence.
C. The contractor shall provide all needed materials to make the connection to the existing
water system. The City shall perform the tap connection for all new distribution pipe of
twelve inches (12") or less. Live tap connections for all new distribution pipe larger than
twelve inches (12") shall require a third -party contractor with qualifications approved by
the City. This connection will be at the expense of the developer or contractor and must be
observed and inspected by the City's Water Department personnel.
D. Prior to the City making the hot tap connection, a tapping sleeve with a test plug shall be
tested following all manufacturer requirements and recommendations, including but not
limited to a hydrostatic test to verify the seal between the gasket and pipe.
E. It shall be the contractor's responsibility to install the tapping sleeve according to the
approved Plans. Any variation from the approved plans, such as a different location or size,
shall be requested through the Design Engineer, and approved by the City. Work by the
City's tapping crew shall not be construed to represent compliance with the Plans or
inspection or approval by the City for any variations from the approved Plans.
Section 402 — Hydraulic Valves:
Add Sections 2.1.D through 2.1.1-1 as follows:
2.1—Valve Size, Type, and Strength:
D. Between the private fire suppression system and the City's potable water system. The
division valve shall be rated at or above 200 psi.
E. Gate valves are required for distribution pipe less than 12 inches in diameter.
F. Butterfly valves are required for distribution pipe of 12 inches in diameter or larger.
G. If system operating pressures are expected to exceed 100 psi, a valve with a working
pressure equal to or greater than the test pressure shall be required.
H. Under special circumstances a 12 -inch gate valve may replace the butterfly valve, under
approval of City Engineer.
17
Add Sections 2.2.A.7 and 2.2.A.8 as follows:
2.2 — Resilient Seated Gate Valves:
A. Resilient Seated Gate Valves and Reduced Wall Resilient Seated Gate Valves for Water
Supply Service: ANSI/AWWA C 509 and/or ANSI/AWWA C 515 (ductile iron only):
7. Pressure Class: Minimum 250 psi
8. Manufacturer: Kennedy Valve Co., Mueller, Clow Valve Co., or City approved
equivalent.
Add Section 2.3.A.10 as follows:
2.3 — Butterfly Valves:
A. Rubber Seated Butterfly Valves: ANSI/AWWA C 504
10. Manufacturer: Kennedy Valve Co., Mueller, Clow Valve Co., or City approved
equivalent.
Add Section 2.4.A.5 as follows:
2.4 — Air Release, Air/Vacuum and Combination Air Valves:
A. Air Release/Air Vacuum and Combination Air Valves for Waterworks Service: ANSI/AWWA
C 512.
5. Manufacturer and Model: Val -Matic 200 Series Single Body Combination Valve
20xC.xx or DeZURIK/APCO series 14xC Single Body Combination Valve or City approved
equivalent.
Replace Section 2.7.E with the followi
2.7 — Valve Boxes:
E. Detail: City of Chubbuck Standard Drawing CSD -405 (Valve Box and Lid)
Add Section 2.9 as follows:
2.9 — Mechanical Restraints:
A. Application: All mechanical joint valves below grade shall be mechanically restrained using
mechanical restraints meeting the requirements of ISPWC Section 401.2.9. Mechanical
restraints shall be in addition to thrust blocks.
Replace Sections 3.2.A and 3.2.13 with the following:
3.2 — Installation:
A. Install valves and appurtenances in accordance with manufacturer's recommendations and
the Standard Drawings and the City of Chubbuck Standard Drawings.
18
B. Install valves plumb and vertical. Set valve box centered and plumb over wrench nut and
flush with ground or street surface. Install box per City of Chubbuck Standard Drawing
CSD -405 (Valve Box and Lid).
Section 403 — Hydrants:
Add Sections 2.2.A.8 and 2.2.A.9 as follows:
2.2 — Fire Hydrant:
A. Dry Barrel Fire Hydrants: ANSI/AWWA C 502
8. Manufacture: Clow Medallion, Mueller Centurion, Kennedy K81 -D, or 5-1/4" Waterous
Pacer.
9. Fire hydrants shall be furnished with a five -inch (5") by four -half inch (4-1/2") NST
"Hydra Storz" Adapter or approved equal, compete with a self-closing butterfly valve
assembly.
Add Section 2.3.13 as follows:
2.3 — Color:
B. Fire hydrants shall be factory painted yellow
Rer lace Section 3.2.13 with the followi
3.2 — Installation:
B. Install fire hydrant in accordance with manufacturer's recommendations and City of
Chubbuck Standard Drawing CSD — 404 (Fire Hydrant) with pumper outlet nozzle facing the
street.
Add Section 3.2.H as follows:
H. Locate wire along the fire hydrant lateral shall interconnect to the locate wire of the
distribution pipe with 3M DBR direct bury splice kit or City approved equivalent and shall
be watertight to provide electrical continuity. The locate wire shall terminate behind the
fire hydrant connecting to a Snakepit tracer box style CD14*TP with blue locking cover.
Section 404 — Water Service Line and Meters:
Add Sections 2.1.D as follows:
2.1— Pipe and Fittings Size, Type and Strength:
D. Pipe larger than two inches (2") in diameter shall meet the requirements of the water pipe
and fittings specified ISPWC Section 401.
19
Replace Section 2.2.A.4 with the following:
2.2 —Service Pipe:
A. Polyethylene (PE) Pressure Pipe for Water Service: ANSI/AWWA C 901
4. Standard PE Code Designation: PE 4710 or ASTM D 3350
Add Section 2.2.A.5 as follows:
5. Color: Blue
Replace Sections 2.2.13 and 2.2.0 with the followi
B. Seamless Copper Water Tube Not Allowed
C. Polyvinyl Chloride (PVC) Service Pipe Not Allowed
Replace Section 2.4.A with the followine:
2.4 — Appurtenances:
A. Service Saddles:
1. One inch (1") to two-inch (2") service line fittings (service saddle, corporation stop,
meter setter, etc.) shall be manufactured by Ford or Romac as detailed in the City of
Chubbuck Standard Drawings CSD -401 and CSD -402 (Potable Water Services).
2. All service saddles shall include double strap stainless steel bands. Saddle bodies shall
be iron or brass. Iron service saddle bodies shall be lined and coated with fusion -
bonded epoxy, nylon, or approved substitution per manufacturer's specifications.
Replace Section 2.4.13.3 with the followi
B. Corporation Stops:
3. Product: Per City of Chubbuck Standard Drawings CSD -401 and CDS 402.
Replace Section 2.4.D.5 with the following:
D. Meter Setters:
5. Product: Per City of Chubbuck Standard Drawings CSD -401 and CDS 402.
Replace Section 2.4.F with the following:
F. Locate Wire:
1. Type: (No 12 AWG) single strand 12 -gauge copper clad steel (CCS) wire with blue high
density polyethylene (HDPE) insulated jacket coating for direct bury.
20
Replace Section 3.2.0 with the following:
3.2 — Installation:
C. Install service line, fittings, and meters, and meter boxes in accordance with the
manufacturer's recommendations and City of Chubbuck Standard Drawings CSD -401 and
CSD -402 (Potable Water Services).
Add Sections 3.2.M and 3.2.N as follows:
M. Locate wire shall be secured with suitable tape every 8 to 10 feet along the buried service
pipe. Locate wire shall interconnect to the locate wire of the distribution pipe with 3M DBR
direct bury splice kit or City approved equivalent and shall be watertight to provide
electrical continuity.
Locate wire shall be wrapped multiple times around the vertical portion of the meter
setter with a minimum of 24" of excess wire beyond the upper most wrap as shown on the
City of Chubbuck Standard Drawings CSD -401 and CSD -402 (Potable Water Services).
N. When service lines are required to be abandoned, the service line shall be disconnected at
the point of connection to the distribution pipe and shall be threaded plugged with a brass
plug. The City shall witness that no leaks occur prior to any placement of bedding material.
21
Division 400 — Potable Water
City of Chubbuck Standard Drawings
CSD -401 1" Potable Water Service
CSD -402 2" Potable Water Service
CSD -403 3" to 12" Potable Water Service
CSD -404 Fire Hydrant
CSD -405 Valve Box and Lid
CSD -406 Flush Hydrant
22
Z_
N
EASEMENT LINE
PROPERTY OWNERS
RESPONSIBILITY
CITY'S RESPONSIBILITY
w 0
J Lu
Ow
2 D
W 0
J
w
0
m
1^
zQ
N
uS
z
Z 0 J
oC o
�Z�z�
wozoo
C) U
C7�uJw
5;z zco
OZF-
()f QOO
0-Iia_UZ
FOR PUBLIC
WORKS
CHUBBUCK CONSTRUCTION
I D R H O STANDARDS
1" POTABLE
WATER SERVICE
zU)
�o
_ Q
N
W
Z
O
Lu
U)
LAST REVISED 3/24/2026
STANDARD DRAWING NO:
CSD -401 1 OF 3
SERVICE FOR
ACROSS THE STREET
18" MIN. BETWEEN STAGGERED
CORPORATION STOPS, UNLESS
RECOMMENDED BY MANUFACTURER
WATER MAIN
CURB
DRAINAGE SWALE
PROPERTY LINE
SIDEWALK
36" MIN. BETWEEN INLINE
CORPORATION STOPS, UNLESS
RECOMMENDED BY MANUFACTURER
24" MIN. BETWEEN CORPORATION
STOP TO SPIGOT INSERTION LINE OR
BELL TRANSITION OF THE PIPE,
UNLESS RECOMMENDED BY
MANUFACTURER
TWO SERVICES PER
TRENCH
INDIVIDUAL METER BOX
REQUIRED
'v' CITY'S RESPONSIBILITY
PROPERTY OWNER
EASEMENT LINE ' RESPONSIBILITY
45° TYP.
z_
S MAX.
N
PLAN VIEW
FOR PUBLIC
WORKS
CHUBBUCK CONSTRUCTION
STANDARDS
IORH0
LAST REVISED 3/24/2026
1" POTABLE STANDARD DRAWING NO:
WATER SERVICE I CSD -401 201`3
MATERIAL LIST:
1. WATER MAIN (PVC, HDPE, OR DUCTILE IRON)
2. CORPORATION STOP W/ CC THREADS (FORD F1001 -4 -G -NL)
3. SERVICE LINE (BLUE POLYETHYLENE SIDR-7, SEE MATERIALS SPECIFICATIONS) NO SPLICES OR
FITTINGS ALLOWED BETWEEN CORPORATION STOP AND METER SETTER
4. 1" METER SETTER (FORD VBHC84W-66-44-G W/ STAINLESS STEEL INSERT - FORD 53-72)
5. 1" METER (SUPPLIED BY CITY)
6. SERVICE SADDLE FOR PVC MAIN:
8" PVC (FORD FCD202-905-TAP-CC4) OR (ROMAC 202S - 905 x 1" CC)
10" PVC (FORD FCD202-1 11 0-TAP-CC4) OR (ROMAC 202S - 1110 x 1" CC)
12" PVC (FORD FCD202-1320-TAP-CC4) OR (ROMAC 202S - 1320 x 1" CC)
7. METER BOX - 24" DIA. ADS (CORRUGATED) OR C.M.P.
8. TYPE I PIPE BEDDING PER SECTION -305 OF ISPWC
9. 2 - (8" X 8" X 12") CONCRETE BLOCKS
10. 1" CAP
11. FOR LANDSCAPE AREAS THE METER BOX LID SHALL BE RING, ADAPTER, AND COVER MARKED
"WATER" WITH READ HOLE FOR NEPTUNE R900 V3, MANUFACTURED BY D&L SUPPLY, MODEL
L-2242, OR CITY APPROVED EQUIVALENT.
FOR CONCRETE AREAS THE METER BOX LID SHALL BE A 24" O.D. HEAVY DUTY MANHOLE RING
AND COVER MARKED "WATER" WITH READ HOLE FOR NEPTUNE R900 V3, MANUFACTURED BY
D&L SUPPLY, MODEL B-5024, OR CITY APPROVED EQUIVALENT. A SEPARATE CONCRETE POUR OR
EXPANSION BOARD, LEAVING A 3'x3' SQUARE CENTERED WITH THE LID SHALL BE REQUIRED.
12. LOCATE WIRE (NO. 12 AWG. COPPER CLAD STEEL (CCS) W/ BLUE INSULATED JACKET COATING)
13. 2x4 WOOD MARKER OR 4" - 5" PEELER CORE POST WITH LOCATE WIRE
14. LOCATE WIRE SPLICE CONNECTER (3M DBR DIRECT BURY SPLICE KIT)
SEE MATERIAL SPECIFICATIONS
NOTES:
A. CUL-DE-SAC SERVICE LATERALS MUST FOLLOW THE MOST DIRECT ROUTE POSSIBLE
BETWEEN CORPORATION STOP AND METER BOX.
B. SERVICE LINE CONNECTION MUST BE A MIN. OF 2 FT. BEHIND EASEMENT LINE.
C. METER BOX SLOT MUST NOT REST ON SERVICE LINE.
D. ALL CONSTRUCTION SHALL CONFORM TO THE REQUIREMENTS OF THE CITY OF
CHUBBUCK AND THE IDAHO STANDARDS FOR PUBLIC WORKS CONSTRUCTION (ISPWC).
E. THE CITY OF CHUBBUCK SHALL INSPECT MAIN LINE AND
METER BOX INSTALLATION PRIOR TO BACKFILLING.
F. WHEN USING ROADSIDE DRAINAGE SWALE TYPICAL STREET SECTION SET TOP OF
METER BOX 3" TO 4" ABOVE TOP BACK OF CURB.
CHUBBUCK
IDDH0
FOR PUBLIC
WORKS
CONSTRUCTION
STANDARDS
1" POTABLE
WATER SERVICE
LAST REVISED 3/24/2026
STANDARD DRAWING NO:
CJD -401 3 01` 3
o
Z
J 0
LU Q W
C(co))
U)
Z — o
N Z
�
3N1I 1N3W3Sb'3 >- z W
z m
�O0
PROPERTY OWNERS 9 z v
RESPONSIBILITY a
CITY'S RESPONSIBILITY o cl) U)
z
0 0
LLI owwW
oU) .8L >zZ0
Lu �00�
Oz dUUQ
��
a -
<Lo
d M
OY J N J Z
W Q Q
2 � a
w
� N � � Z
�o� ) Z
�
0H
Z)oW U
U Q M W
z_ Lua- w U)
Q
Z X
g
in �o
M
W
0
Q
� N
r
J
Q U)
z Z
W LL
U) (.0Z_
_ N
CO
CD +
r
r
FOR PUBLIC Cn
WORKS
CHUBBUCK CONSTRUCTION LAST REVISED 3/24/2026
1 D R H 0 STANDARDS 1-1/2" OR 2" POTABLE STANDARD DRAWING NO:
WATER SERVICE CSD -402 1 OF 3
TRENCH LINE
m: m:
U�
Zp
24" MIN. TO CORPORATION STOP FROM
SPIGOT INSERTION LINE OR WHERE BELL
TRANSITIONS TO THE BARREL OF THE
PIPE UNLESS OTHERWISE
RECOMMENDED BY MANUFACTURER
PROPERTY LINE
SIDEWALK'
° � °•e .. l.. . .°all.°,, ° �` ° °°�� °
i
4" TYP.
/ I - 64 �(t CA -
CHUBBUCK
I D R H 0
\ GROUT AROUND
PIPE TYP.
EASEMENT LINE
Jp 2' MIN.
FOR PUBLIC
WORKS
CONSTRUCTION
STANDARDS
1-1/2" OR 2" POTABLE
WATER SERVICE
6" MIN.
ni A K I Xnrini
Z
CITY'S RESPONSIBILITY
PROPERTY OWNERS
RESPONSIBILITY
LAST REVISED 3/24/2026
STANDARD DRAWING NO:
CSD -402 2OF3
z_
9
u
\ GROUT AROUND
PIPE TYP.
EASEMENT LINE
Jp 2' MIN.
FOR PUBLIC
WORKS
CONSTRUCTION
STANDARDS
1-1/2" OR 2" POTABLE
WATER SERVICE
6" MIN.
ni A K I Xnrini
Z
CITY'S RESPONSIBILITY
PROPERTY OWNERS
RESPONSIBILITY
LAST REVISED 3/24/2026
STANDARD DRAWING NO:
CSD -402 2OF3
MATERIAL LIST:
1. WATER MAIN (PVC, HDPE, OR DUCTILE IRON)
2. 1-1/2" CORPORATION STOP W/ CC THREADS (FORD FB1001-6-G-NL)
2" CORPORATION STOP W/ CC THREADS (FORD FB1001-7-G-NL)
3. SERVICE LINE (BLUE POLYETHYLENE SIDR-7, SEE MATERIALS SPECIFICATIONS) NO SPLICES OR
FITTINGS ALLOWED BETWEEN CORPORATION STOP AND METER SETTER
4. 1-1/2" METER SETTER SET FOR 13-1/8" LAY LENGTH (FORD VH76-18-11-66-NL)
W/ STAINLESS STEEL INSERT (FORD 74-DR11)
2" METER SETTER SET FOR 17" LAY LENGTH (FORD VH77-18-11-77-NL)
W/ STAINLESS STEEL INSERT (FORD 75-DR11).
5. 1-1/2" METER W/ 13-1/8" LAY LENGTH (SUPPLIED BY CITY)
2" METER W/ 17" LAY LENGTH (SUPPLIED BY CITY)
6. 1-1/2" SERVICE SADDLE FOR PVC MAIN:
8" PVC (FORD FCD202-905-TAP-CC6) OR (ROMAC 101 S - 905 x 1.5" CC)
10" PVC (FORD FCD202-1 1 10-TAP-CC6) OR (ROMAC 101S - 1110 x 1.5" CC)
12" PVC (FORD FCD202-1320-TAP-CC6) OR (ROMAC 101 S - 1320 x 1.5" CC)
2" SERVICE SADDLE FOR PVC MAIN:
8" PVC (FORD FCD202-905-TAP-CC7) OR (ROMAC 202S - 905 x 2" CC)
10" PVC (FORD FCD202-1 11 0-TAP-CC7) OR (ROMAC 202S - 1110 x 2" CC)
12" PVC (FORD FCD202-1320-TAP-CC7) OR (ROMAC 202S - 1320 x 2" CC)
7. CONCRETE VAULT (HS20 RATED) OR 48" STANDARD MANHOLE W/ FLAT LID & NO CONE (HS20 RATED)
OR 48" CORRUGATED HDPE PIPE OR APPROVED EQUAL MAY BE USED IN LANDSCAPE AREAS.
8. TYPE I OR TYPE III BEDDING PER SECTION 305 OF ISPWC
9. 24" MANHOLE LID AND RING
10. 2" CAP
11. GRADE RINGS
12. LOCATE WIRE (NO. 12 AWG.
COPPER CLAD STEEL (CCS)
W/ BLUE INSULATED JACKET COATING)
13. (2) 2"x8"x12" CONCRETE BLOCKS
14. (6) 4"x8"x16" CONCRETE BLOCKS EVENLY
SPACED AROUND AND BELOW THE VAULT
15. 2x4 WOOD MARKER OR 4" - 5" PEELER CORE
POST WITH LOCATE WIRE
16. LOCATE WIRE SPLICE CONNECTER
(3M DBR DIRECT BURY SPLICE KIT)
SEE MATERIAL SPECIFICATIONS
CHUBBUCK
IDDH0
FOR PUBLIC
WORKS
CONSTRUCTION
NnTFS-
A. CUL-DE-SAC SERVICE LATERALS
MUST FOLLOW THE MOST DIRECT
ROUTE POSSIBLE BETWEEN
CORPORATION STOP AND METER BOX.
B. SERVICE LINE CONNECTION MUST BE
A MIN. OF 2 FEET BEHIND EASEMENT
LINE.
C. ALL CONSTRUCTION SHALL CONFORM
TO THE REQUIREMENTS OF THE CITY
OF CHUBBUCK AND THE IDAHO
STANDARDS FOR PUBLIC WORKS
CONSTRUCTION (ISPWC).
D. THE CITY OF CHUBBUCK SHALL
INSPECT MAIN LINE AND METER BOX
INSTALLATION PRIOR TO BACKFILLING.
LAST REVISED 3/24/2026
STANDARDS 1-1 /2" OR 2" POTABLE STANDARD DRAWING NO:
WATER SERVICE I CSD -402 3 OF 3
z
O
zp �
M w
Q =
LL
ww w
> Z z
U W O
LLJ
� Z p O
Q W �-
LJ
� � Z �
� �
w
U
Y n -
W 2 J
U > p O
Qwz�
m p Q � ,
M w m
z O —
O_wZ
p O
Lu U)
z
ocl
�0W
W
Z 2
�UL�
w
ao
LL w
Y Z J
O Z O
>
mOU>0
%
LV
Z
M
Z
PROPERTY OWNERS
Q
RESPONSIBILITY
CITY'S RESPONSIBILITY
W
U)
co
Lo
L
CD
Q
- Y I—
w
>
Z
QO>
p W
zX
}m
PROPERTY LIN
in
'NIN
..9
LU
� p
Q
�
N (�
N
z
ti
r
N
FOR PUBLIC
WORKS
LAST REVISED
3/24/2026
CHUBBUCK CONSTRUCTION
STANDARDS
3" TO
12" POTABLE
STANDARD DRAWING NO:
D R H O
WATER SERVICE
CSD
-403 1 OF 3
z
O
zp �
ww w
> Z z
� Z p O
Q W �-
� � Z �
� �
w
U
Y n -
U > p O
Qwz�
m p Q � ,
w
U WO
LLJ 0 p F
Z �5
0 LLJ W —
❑ O m
wOzaz
w -—�
d U _j W
�z<�
O0>�
Y U W W
U ❑ � z
W
mQ�;O
Ml
z ❑ } (If
O z m z
zQLu�:
Lu z O
LU Lu
U Q W
O > �
LuCL
Y ❑
U
Q
m
*
*
z z
PROPERTY OWNERS
RESPONSIBILITY }
CITY'S RESPONSIBILITY
W_
w0� Q
— W J
/ < Z
L p U
a °/ �0LL
H
U
co ® ** Q Q
3' MIN. **3'MIN.** ❑ >
IM wD
x�*
No
�inih O
O❑x
W ~ Z
PROPERTY LINEW z_ >- a U)
J J
ch zmJz
} * w(-na W
H Z H 2
N z 0 W
W
U)
Or,0p
L \ w
w0}Z
> p z
W �- o
Z
z_ %—❑��
❑ LL J z 2 W w
r W LU J (n Z L)
❑ _
Q U �= 0U Q N
W W U W
m U
Z z H
4.
FOR PUBLIC N
WORKS
CHUBBUCK CONSTRUCTION
STANDARDS
IORH0
LAST REVISED 3/24/2026
3" TO 12" POTABLE STANDARD DRAWING NO:
WATER SERVICE CSD -403 2OF3
T MIN. T MIN.
z ❑ } (If
O z m z
zQLu�:
Lu z O
LU Lu
U Q W
O > �
LuCL
Y ❑
U
Q
m
*
*
z z
PROPERTY OWNERS
RESPONSIBILITY }
CITY'S RESPONSIBILITY
W_
w0� Q
— W J
/ < Z
L p U
a °/ �0LL
H
U
co ® ** Q Q
3' MIN. **3'MIN.** ❑ >
IM wD
x�*
No
�inih O
O❑x
W ~ Z
PROPERTY LINEW z_ >- a U)
J J
ch zmJz
} * w(-na W
H Z H 2
N z 0 W
W
U)
Or,0p
L \ w
w0}Z
> p z
W �- o
Z
z_ %—❑��
❑ LL J z 2 W w
r W LU J (n Z L)
❑ _
Q U �= 0U Q N
W W U W
m U
Z z H
4.
FOR PUBLIC N
WORKS
CHUBBUCK CONSTRUCTION
STANDARDS
IORH0
LAST REVISED 3/24/2026
3" TO 12" POTABLE STANDARD DRAWING NO:
WATER SERVICE CSD -403 2OF3
MATERIAL LIST:
1. WATER MAIN (PVC, HDPE, OR DUCTILE IRON).
2. TAPPING VALVE OR FLANGED X M.J. VALVE (SEE MATERIAL SPECIFICATIONS)
3. 4" TO 12" SERVICE LINE (PVC OR DUCTILE IRON)
4. 4" TO 12" FLANGED GATE VALVES
5. 3" TO 12" METER (SUPPLIED BY CITY) ...T' METER SHALL REQUIRE 4"x3" FLANGED REDUCERS EACH
SIDE OF THE METER. ADJUST THE SIZE OF VAULT TO ACCOMMODATE THESE EXTRA FITTINGS. SEE
SHEET 2 OF 3 FOR SEPARATION REQUIREMENTS""
6. 3" TO 12" STRAINER
7. CONCRETE VAULT, SIZED TO ACCOMMODATE METER AND FITTINGS AS SHOWN ON SHEET 2 OF 3.
8. 3/4" MINUS AGGREGATE BEDDING
9. SUPPORT JACKS
10. 4" TO 12" ROMAC COUPLING OR APPROVED EQUIVALENT CONNECTION
11. 24" MANHOLE LID AND RING
12. TAPPING SLEEVE (ROMAC SST, MUELLER H304, OR FORD FAST) OR FLANGED X M.J. TEE.
13. VALVE BOX
14. FLANGED COUPLING ADAPTERS WITH MECHANICAL RESTRAINT
15. FLOOR DRAIN
16. LOCATE WIRE (NO. 12 AWG. COPPER CLAD STEEL (CCS) W/ BLUE INSULATED JACKET COATING)
17. LOCATE WIRE SPLICE CONNECTER (3M DBR DIRECT BURY SPLICE KIT)
SEE MATERIAL SPECIFICATIONS
18. CONCRETE THRUST BLOCK PER ISPWC SPECIFICATIONS
A I/'1TC C'.
A. CUL-DE-SAC SERVICE LATERALS MUST FOLLOW THE MOST DIRECT ROUTE POSSIBLE BETWEEN
TAPPING TEE AND METER VAULT.
B. SERVICE LINE CONNECTION MUST BE 2 FT. BEHIND METER VAULT
C. POSITION SUPPORT JACKS TO ALLOW FOR MAINTENANCE.
D. SIZE ON SIZE REQUIRE A MUELLER TAPPING SLEEVE OR APPROVED EQUIVALENT.
CHUBBUCK
IDDH0
FOR PUBLIC
WORKS
CONSTRUCTION
STANDARDS
LAST REVISED 3/24/2026
3" TO 1211 POTABLE STANDARD DRAWING NO:
WATER SERVICE I CSD -403 3 OF 3
vi
� �_
Z
W W}❑ N
U= 2 W r
O H
W W
U¢JO Z U
~w
U) W
Q W Z
❑ O
J p=
d m
Q
of =)
QOL`3:
Xi
MATERIAL LIST:
1. TEE (FLG X MJ)
2. GATE VALVE (FLG X MJ)
3. (2" X 8" X 12") CONCRETE BLOCK
4. CONCRETE THRUST BLOCK PER ISPWC SPECIFICATIONS
5. FIRE HYDRANT, FACTORY PAINTED YELLOW
COMPRESSION TYPE (M.J.) PRODUCTS SUCH AS CLOW - MEDALLION, OR
MUELLER - CENTURION, KENNEDY - K81 -D, OR 5-1/4" WATEROUS PACER
6. TYPE I BEDDING PER SECTION 305 OF ISPWC
7. CAST IRON VALVE BOX (SEE CITY OF CHUBBUCK STANDARD DRAWING CSD -405)
8. FIRE HYDRANT SERVICE LINE LATERAL (6" DIAMETER PIPE, DUCTILE IRON OR
PVC)
9. LOCATE WIRE (NO. 12 AWG. COPPER CLAD STEEL (CCS) W/ BLUE INSULATED
JACKET COATING)
10. LOCATE WIRE ACCESS POINT (SNAKEPIT TRACER BOX STYLE CD14- TP W/ BLUE
LOCKING COVER)
11. LOCATE WIRE SPLICE CONNECTER (3M DBR DIRECT BURY SPLICE KIT) SEE
MATERIAL SPECIFICATIONS
12. MECHANICAL RESTRAINT IN ADDITION TO THRUST BLOCKS
A. HYDRANTS SHALL BE LOCATED AT THE STREET INTERSECTION OR AT THE LOT LINE
BETWEEN ADJACENT PROPERTIES. THE HYDRANT SHALL BE INSTALLED SO THAT
THE FLANGE IS 2" MIN. AND 8" MAX. ABOVE FINISHED GRADE.
B. CUL-DE-SAC SERVICE LATERALS MUST FOLLOW THE MOST DIRECT ROUTE POSSIBLE
BETWEEN TAPPING TEE AND HYDRANT.
C. ALL ANCHORS AND BLOCKING TO BEAR AGAINST UNDISTURBED SOIL.
CHUBBUCK
IDDH0
FOR PUBLIC
WORKS
CONSTRUCTION
STANDARDS
FIRE HYDRANT
LAST REVISED 3/24/2026
STANDARD DRAWING NO:
CSD -404 2 OF 2
- / I - 64-�-4 c \ —
CHUBBUCK
I D R H 0
24" DIA.
FOR PUBLIC
WORKS
CONSTRUCTION
STANDARDS
MATERIAL LIST:
1. 5-1/4" VALVE BOX LID ACCORDINGLY MARKED
"WATER" OR "IRRIGATION"
2. CONCRETE COLLAR (24" DIA. x 6" TALL)
3. (2) #4 REBAR HORIZONTAL HOOPS W/ (4) #4 REBAR
VERTICALS
4. VALVE
5. CAST IRON VALVE BOX RISER
6. LOCATE WIRE (NO. 12 AWG. COPPER CLAD STEEL
(CCS) W/ INSULATED JACKET COATING)
7. LOCATE WIRE SPLICE CONNECTER AT MAINLINE
TEE OR CROSS LOCATIONS (3M DBR DIRECT BURY
SPLICE KIT) SEE MATERIAL SPECIFICATIONS
8. IN LIEU OF #4 REBAR IN CONCRETE COLLARS,
3 -POUNDS OF FIBRILLATED POLYPROPYLENE
FIBER PER CUBIC YARD OF CONCRETE MAY BE
USED FOLLOWING ISPWC 703.2.2.E.
VALVE BOX AND LID
LAST REVISED 3/24/2026
STANDARD DRAWING NO:
CSD -405 1 OF 1
FINISH GRADE
5' MIN.
6' MAX.
PROVIDE T OF EXTRA
LOCATE WIRE INSIDE
OR BELOW ACCESS
POINT
v
�J
as
°
UNDISTURBED
,
6 ' % EARTH OR THRUST
1 2
4 8 BLOCK PER ISPWC
SPECIFICATIONS
SECTION VIEW
MATERIAL LIST:
1.
WATER MAIN (SIZE AND TYPE VARIES)
2.
UNI -FLANGE PIPE RESTRAINT SERIES 1300
3.
(2) 3/4" ANCHOR BOLTS ON 6" WATER MAIN OR SMALLER,
NOTES:
OR (4) 3/4" ANCHOR BOLTS ON 8" WATER MAIN,
SECURELY FASTENED TO EYE BOLTS.
A. FLUSHING HYDRANT SHALL BE ONLY
USED AS TEMPORARY BASIS UNTIL
4.
MAIN SIZE X 2" FL REDUCER
DEVELOPMENT CONTINUES
CONNECTING TO THE EXISTING
5.
2" GALVANIZED 90° ELBOW
WATERLINE.
6.
2" GALVANIZED PIPE, THREADED ON BOTH ENDS
7.
2" MAINGUARD NO. 77 BLOW -OFF HYDRANT W/ 2-1/2" NST
NOZZLE OR APPROVED EQUAL. LOCATE OUT OF
ROADWAY BEHIND NEW CURB & GUTTER.
8.
2" COMPANION FLANGE CAP TAPPED 2" F.I.P.
9.
HAMMERHEAD THRUST BLOCK, MIN 10.3 SQ. FT.
10.
EYE BOLTS SECURELY FASTENED TO PIPE RESTRAINT
11.
LOCATE WIRE (NO. 12 AWG. COPPER CLAD STEEL (CCS)
W/ BLUE INSULATED JACKET COATING)
12.
LOCATE WIRE ACCESS POINT (SNAKEPIT TRACER BOX
STYLE CD14* TP W/ BLUE LOCKING COVER)
FOR PUBLIC
WORKS
LAST REVISED 3/24/2026
CHUBBUCK CONSTRUCTION
STANDARDS
STANDARD DRAWING NO:
I D D H O
FLUSH HYDRANT
CSD -406
1 OF 1
Division 500 — Sanitary Sewer
General Information:
Sanitary Sewer Pipe:
A. All such sanitary sewer pipe extension and installations shall be in dedicated public right of
way areas. All sanitary sewer pipe extensions/installations shall conform in all respects to
the standards, specifications, and material requirements set forth in these standards and
the ISPWC.
B. Sizing:
In areas with new development, the City of Chubbuck may require an engineering report
to verify adequate wastewater flows. The sewer system shall be designed for the
estimated ultimate build -out flow. The anticipated design shall include the average and
design peak flows of residential, industrial, or commercial areas. The plan shall show the
location, size, and direction of flow of relevant existing and proposed sanitary and
combined wastewater draining.
Sewer systems shall be designed in compliance with the "Recommended Standards for
Wastewater Facilities" promulgated by the Great Lakes - Upper Mississippi River board of
state public health and environmental managers and published by the Health Education
Services, Albany, New York.
Gravity sewer pipe shall follow City of Chubbuck current facility planning study and/or
master plan. Sewer pipe larger than 8 inches shall be based on flows, not to justify flatter
slopes.
C. Dead End:
Gravity sewer pipe stubbed for future use shall provide a sewer cleanout to perform all
required testing procedures per the ISPWC. In areas where the sewer cleanout could be
damaged by either snow removal or any other means, a traffic rated cleanout shall be
required.
D. Inside Easements:
The City of Chubbuck may require or allow sanitary sewer mains to be installed in utility
easements if it is deemed necessary for the good of the sewer system.
Access to all public sanitary sewer pipe and manholes deeper than eight feet (8') shall
provide an easement of no less than thirty feet (30') in width, centered over the sewer
structure to maintain fifteen feet (15') from the easement sideline. Easement width may
be reduced to twenty feet (20') if the sewer structures are shallower than eight feet (8'),
unless they are located within areas dedicated to the public. Narrower easements may be
36
allowed by the City in special circumstances when it can be demonstrated that the pipes
and/or manholes can be properly maintained by the City without introducing additional
risk to the City.
E. Pipe Cover:
All public gravity sewer pipe shall have a minimum depth of four feet (4') from top of pipe to
finish grade.
Sanitary Sewer Manhole:
A. Location:
All public sewer manholes must be accessible for operations and maintenance. Location of
each sewer manhole should be in the public road right of way or must be accessible with a
heavy truck / cleaning equipment either by path or private roadway requiring approval
from the City Engineer and Sewer Superintendent.
B. Pipe Orientation:
Manhole design shall require that the angle between any incoming (inlet) pipe and the
outgoing (outlet) pipe be 90 degrees or greater.
C. Channel:
At all sewer pipe connections to the sewer manhole, a concrete channel shall be formed in
the base of the manhole to ensure smooth and efficient, sanitary sewage flow from the
inlet pipe to the outlet pipe, with no sharp angles, using a consistent, large -radius curve if a
change in direction is required.
Sewer Service Line:
A. Sizing:
All sewer service connections to public sanitary sewer shall be a minimum of four inches
(4") in diameter.
B. Separate Lines Required:
A separate and independent private sewer shall be provided for every building, residence,
or property unless specific permission is obtained from City of Chubbuck.
It shall be unlawful for any person to extend any private sewer beyond the limits of the
building or property for which a permit has been given without obtaining permission from
City of Chubbuck. The existence of a private sewer permit shall in no way be construed as
making permissible any work for which an excavation permit may be required.
37
C. Repairs:
When any private sewer connected with any public sewer becomes obstructed, broken or
out of order, the owner, agent, or tenant of such premises shall repair same at the owner's
expense. This cost shall include the service tap or connection to the main public sewer as
well as the total length of service line or private sewer from such service tap or connection
to the point at which sewage is introduced into the service for the premises. This cost shall
also include the replacement of street, curb and gutter, sidewalk or any other
improvement disturbed by the repair of any private sewer or service connection. No
person shall construct, relay, repair or extend any private sewer until the person making
the same shall obtain a private sewer permit from the proper issuing agency or
department of the City of Chubbuck.
Section 501— Gravity Sewers:
Replace Section 2.2 with the following:
2.2 — Gravity Sewer Pipe and Fittings:
A. Solid Wall PVC Pipes Sizes 4 inch through 15 inch: ASTM D 3034
5. Minimum Wall Thickness: SDR 35
6. Joints: Joints with ASTM F 477 Elastomeric gaskets
7. Color: Green
B. Solid Wall PVC Pipes Sizes 18 inch through 36 inch: ASTM F 679
1. Minimum Wall Thickness: SDR 35
2. Joints: Joints with ASTM F 477 Elastomeric gaskets
3. Color: Green
C. Pressure Pipe for Gravity Sewer
1. PVC Pipe: AWWA C900-16 Class 100 psi or higher 4"-60", or ASTM D2241 Class 160 psi
or higher. Match the inside diameter of the connecting non -pressure pipe, plus or
minus 0.125 inches.
Section 502 — Manholes:
Add Section 2.1.D as follows:
2.1— Manhole Size, Type, and Strength:
D. Manhole cones shall be concentric.
Replace Section 2.3 with the following:
2.3 — Steps:
A. No steps shall be placed in manholes.
38
Replace Section 2.6 with the following:
2.6 — Collars:
A. Concrete Collars: Class 4000 psi per ISPWC Section 703 — Cast -in -Place Concrete.
Add Section 2.8.0 as follows:
2.8 — Mortar and Grout:
C. Any holes shall be filled and made smooth with a non -shrink grout.
Replace Section 3.5.A.2.b with the following:
3.5 — Placement of Manhole Bases:
A. Cast -In-place Manhole Bases
2. Over Existing Mains:
b. Prior to cutting the existing pipe, construct the base and channel so wastewater
can flow freely per Details SD -501 through SD -503. Once the new manhole has
been pressure tested with City acceptance, saw cut the existing pipe to the spring
line and remove top portion of the pipe.
Section 504 — Sewer Services:
Replace Section 2.2.0 with the following:
2.2 — Pipe and Fittings:
C. ABS Sewer Pipe and Fittings: ASTM F628
1. Minimum Wall Thickness: Schedule 40
2. Joints: Glued per manufacture's recommendations
3. Pipe transition and connection to wye fitting shall be submitted to and approved by
the City.
4. Gasketed deep bell bends are required for Type "E" sewer service installations per SD -
511. If such fittings are unavailable, this type of service line shall not be allowed for
Type "E" sewer service installation.
Replace Section 2.2.D with the following:
D. PVC Sewer Pipe and Fittings (other than ASTM D 3034): ASTM D 1785
1. Minimum Wall Thickness: Schedule 40
2. Joints: Glued per manufacture's recommendations
3. Pipe transition shall be submitted to and approved by the City.
39
Replace Sections 3.3.A.3 through 3.3.A.5 with the following:
3.3 — Connection to Main:
A. Connections for new main pipeline or pipeline replacement:
3. New sewer connection to the main shall have a prefabricated wye fitting. Flexible
tapping saddles for a new connection will not be allowed unless approved by City
Engineer or Sewer Superintendent.
4. Location of the service connection at the main shall be no closer than five feet (5') to
the outside of the manhole.
5. Distance between service line connections along the main shall be no closer than two
feet (2') from outside of hole to outside of hole between connections.
6. Sewer Service connections to manholes are Not Allowed.
Remove Sections 3.3.A.6 through 3.3.A.9 in its entirety:
Add Section 3.3.D as follows:
3.3. — Connection to Main
D. Type "C" and Type "F" Sewer Service Line Connections as shown on SD -511 are NOT
allowed.
Replace Section 3.4 with the followi
3.4 — Connection to Existing Manhole:
A. Sewer Service connections to existing manholes are Not Allowed. Four inch (4") connections
shall be made with a saddle connection to the sewer mainline.
40
Division 700 — Concrete
General Information:
Concrete Mix:
A. All concrete placed for public improvements, such as for sidewalks, pavement, curb, curb and
gutter, valley gutters, manholes, manhole and valve collars, etc., shall be Class 4000AF or
4000BF concrete with 3/4 inch minus coarse aggregate in accordance with Section 703,
unless the design engineer determines a higher strength concrete class is required.
Section 703 — Cast -In -Place Concrete:
Realace Section 2.4.D with the following:
2.4 —Concrete Mix
D. Unless otherwise approved by the City Engineer, use Class 4000AF or 4000BF concrete with
3/4 inch minus coarse aggregate. This concrete class is required for public improvements
such as pavement, sidewalks, curb, curb and gutter, valley gutters, manhole and valve
collars, etc., unless the design engineer determines a higher strength concrete class is
required.
Add Section 3.2.C.4 as follows:
3.2 — Weather and Temperature Limitations:
C. Cold Weather Limitations and Concreting Procedures:
4. In cold weather conditions, for the installation of concrete curb or sidewalk, in or along
the public right of way, additional measures and special protection shall be made to
prevent the concrete from being affected by the exposure of cold weather. This shall
include but is not limited to ensuring the ground is not frozen. Contractor shall take
additional measures to keep the concrete warm, either with insulation, heaters, and/or
enclosures. Quality -control inspections described in this section may also be verified by
the City, but if so, shall not remove the responsibility from the contractor. Additional
inspection fees may be required at the expense of the contractor. If said protection
and testing results are insufficient, the City may reject the newly installed concrete.
41
Section 706 — Other Concrete Construction:
Replace Section 2.4.A.4 with the followi
2.4 — Portland Cement Concrete:
A. Conform to the requirements of Section 703 - Cast -In -Place Concrete and Section 705 -
Concrete Pavement, except use the following classes of concrete:
4. All concrete placed for public improvements, such as for sidewalks, pavement, curb,
curb and gutter, valley gutters, manholes, manhole and valve collars, etc., shall be Class
4000AF or 4000BF concrete with 3/4 inch minus coarse aggregate in accordance with
Section 703, unless the design engineer determines a higher strength concrete class is
required.
Add Section 3.14 as follows:
3.14 - Detectable Warning Domes:
A. Detectable Warning Domes used in sidewalks shall be constructed of a prefabricated
composite material. Metal, rubber, or ceramic detectable warning dome materials are not
permitted. Detectable warning domes shall be yellow in color unless approved otherwise by
the City. Cast iron detectable warning domes panels may be used in specific areas following
approval by the City.
Detectable Warning Domes shall meet the requirements of the current version of the Public
Right of Way Access Guidelines (PROWAG).
Detectable Warning Domes shall extend the full width of the ADA -accessible route (throat
width of pedestrian ramp or full width of the pedestrian access route).
Add Section 3.15 as follows:
3.15 — Curb Utility Markings:
A. During the placement of new concrete curb, utility marking shall be embossed into the top
of the curb. The marking shall be two inch (2") high letters and be either "SS" for sanitary
sewer, "W" for water, or "I" for irrigation. The stamp shall be placed into the concrete
before the concrete sets up. The letters shall be facing the street and indicate the location
of the utility crossing at the curb.
42
Division 700 — Concrete
City of Chubbuck Standard Drawings
CSD -701 Concrete Ribbon Curb
CSD -702 Concrete Scupper
CSD -703 Commercial Approach
43
I
I
I/
I
ASPHALT PER
STREET DESIGN
3"
12"
4" THICK CONCRETE
(6" THICK CONCRETE
THROUGH DRIVEWAY AREA)
1.5% TO 2.00%
f
FINISH GRADE OF
DRAINAGE SWALE
(TOP OF SOD OR
ROCK LANDSCAPING)
MATCH ROAD DESIGN R=1/2"
CONCRETE iT��n CD
RIBBON CURB
a a a a a a a
4" OF 3/4" MINUS
CRUSHED BASE
MATERIAL AS PER
ISPWC SECTION 800
- /ac -f-- I\-
r.NUReuru
1 9 A H 0
FOR PUBLIC
WORKS
CONSTRUCTION
STANDARDS
� PEEP
12" v
' , -`/v-
P/,
l `,'RFq
4" OF 3/4" MINUS
CRUSHED BASE
MATERIAL AS PER
ISPWC SECTION 800
NOTES:
A. MATERIALS AND CONSTRUCTION IN COMPLIANCE
WITH ISPWC AND CITY OF CHUBBUCK
SPECIFICATIONS.
B. BASE TO BE COMPACTED TO EXCEED 95% OF
STANDARD DENSITY.
C. SLOPE SIDEWALK TOWARDS THE STREET NOT TO
EXCEED 2% UNLESS OTHERWISE APPROVED BY
CITY OF CHUBBUCK.
D. CONTINUOUS PLACEMENT PREFERRED, SCORE
INTERVALS 10 -FEET MAXIMUM SPACING.
E. CONTACT CITY OF CHUBBUCK PRIOR TO PLACING
CONCRETE.
CONCRETE
RIBBON CURB
LAST REVISED 3/24/2026
STANDARD DRAWING NO:
CSD -701 1 OF 1
1/2"
EXPANSION--,,
BOARD
6911
B
4'-8"
4" 4'-0"
#4 REBAR SPACED @
1/2" 10" O.C. EACH WAY
EXPANSION
4
BOARD
SIDEWALK J o
5"
4" OF 3/4" MINUS
CRUSHED BASE
MATERIAL AS PER
ISPWC SECTION 800
FOR PUBLIC
WORKS
CHUBBUCK CONSTRUCTION
STANDARDS
IDDH0
VARIES
4"
T-10"
SECTION VIEW A -A
CONCRETE
SCUPPER
4"
#4 REBAR SPACED
@ 10" O.C. EACH WAY
1/2"
EXPANSION
BOARD
WALK
1/2"
EXPANSION
BOARD
SIDEWALK
LAST REVISED 3/24/2026
STANDARD DRAWING NO:
CSD -702 1 OF 2
B
WALK
A
SIDE
° 'A
I
B
4'-8"
4" 4'-0"
#4 REBAR SPACED @
1/2" 10" O.C. EACH WAY
EXPANSION
4
BOARD
SIDEWALK J o
5"
4" OF 3/4" MINUS
CRUSHED BASE
MATERIAL AS PER
ISPWC SECTION 800
FOR PUBLIC
WORKS
CHUBBUCK CONSTRUCTION
STANDARDS
IDDH0
VARIES
4"
T-10"
SECTION VIEW A -A
CONCRETE
SCUPPER
4"
#4 REBAR SPACED
@ 10" O.C. EACH WAY
1/2"
EXPANSION
BOARD
WALK
1/2"
EXPANSION
BOARD
SIDEWALK
LAST REVISED 3/24/2026
STANDARD DRAWING NO:
CSD -702 1 OF 2
#4 REBAR SPACED @
10" O.C. EACH WAY SLOPE TOWARDS
STREET
4 1.5% TO 2.00% FINISH GRADE
FINISH GRADE - — — 4" MIN. (TOP OF SOD /
(TOP OF SOD /
LANDSCAPILANDSCAPING)
NG)
°
2"
2'•
3"
SLOPE TOWARDS
POND AREA 4" OF 3/4" MINUS
1.5% TO 2.00% CRUSHED BASE
MATERIAL AS PER
ISPWC SECTION 800
SECTION VIEW B -B
TOP OF SIDEWALK
1/2"
EXPANSION
BOARD
#4 REBAR SPACED @
10" O.C. EACH WAY
f 4" MIN.
FOR PUBLIC
WORKS
CHUBBUCK CONSTRUCTION
STANDARDS
IOHH0
3
—° 1
ELEVATION
1/2"
EXPANSION
BOARD
FINISH GRADE (TOP
OF SOD OR ROCK
LANDSCAPING)
A. MATERIALS AND CONSTRUCTION IN COMPLIANCE
WITH ISPWC AND CITY OF CHUBBUCK
SPECIFICATIONS.
B. BASE TO BE COMPACTED TO EXCEED 95% OF
STANDARD DENSITY.
C. SLOPE SIDEWALK TOWARDS THE STREET NOT TO
EXCEED 2% UNLESS OTHERWISE APPROVED BY
CITY OF CHUBBUCK.
D. TOP SURFACE TO BE BROOM FINISHED.
E. ALL EXTERNAL CORNERS SHALL BE TROWELLED
WITH 1/4" RADIUS EDGER.
F. CONTACT CITY OF CHUBBUCK PRIOR TO PLACING
CONCRETE.
LAST REVISED 3/24/2026
CONCRETE STANDARD DRAWING NO:
SCUPPER CSD -702 2 OF 2
§
2
LL
/
0
F-
§
/
z
± ¥
Oz
\
00
e>-
i
o
z
i
<
0
�
\ �
LL
\/
w
\
Z�/
<
I
«Iw
\�
�
k
§}
6
}
/
F-
@/
m�
/O
2
i
II
\ƒ
E
$
R
�
0
jwE
2a-0
7
0
0 <
«ƒ
m
o
± E
z
\
ƒ
ƒ < /
\c
f§
\i
x
Lu
I m
U)
E
k
7�
Cl
2
o
0
I
\
0
i
z
\Lu
\�
/
<
/�
§
i
co
o
\�/
f/
/
/m
b
0§
§
-0
��
�0
/
\
\ƒj
��
\�
E
�\
\7
LU
k/
/
�c
}�
\i
Lu
7)cd
�
//
//
�\
\\
eW
<
o>
7E=
F- C)
OL
50
jU)
§�
w\
0
ji
/E
Lu
=
0
2 z
±o
e$
<I
= z
<E
0 0=
E
o
_,
=7
z z
00
cc
Co
=\2
2
EO
2»
=E
—ixI
w w 0
e
<
00
z
-J _j
/
u
«
a
d
6
E
z
d
ƒ�
I
mw§}
F-
W
2
=
\ \�o
i§?/
/
Lu
0
\ /\/
0
}ƒ\$
>
2
\//
/b/\
>z
\\/
I0 E CL
w()w
�0-\
�p�
@�
0
�o
/
IQo
�
ƒ%f
/
§ �F
0
o f
7
\/ m
0
ƒ
'
FOR PUBLIC
WORKS
LAST
REVISED
3/24/2026
CHUBBUCK
CONSTRUCTION
NO:
STANDARDS COMMERCIAL STANDARD DRAWING
IDRH]
APPROACH
CS D_703
1OF1
Division 800 — Aggregates and Asphalt
General Information:
Asphalt Mix:
A. For all asphalt placed for public improvements in or outside the public right of way, such as for
walking paths, road surface, etc., the type of asphalt mix design shall be identified on the
construction plans either on a street cross section or a construction call out. Construction
plans/notes shall also indicate thickness and type of road base and subbase material and
subgrade separation fabric.
Section 810 — Plant Mix Pavement:
Add Section 2.1.1 and Section 2.1.J as follows:
2.1— Hot Mix Asphalt Design:
Plant mix pavement shall be Superpave HMA Class SP3 with 1/2" minus aggregate. Percentage
of RAP by total weight of aggregate shall not exceed 22 percent. Up to 17 percent of RAP by
weight of the total binder in the plant mix may be used.
A minimum of five (5) business days prior to installation, the contractor shall submit to the City
of Chubbuck, for approval, a job mix formula for each mix required on the project. The job mix
formula shall be prepared by an independent testing laboratory approved by the City of
Chubbuck.
Replace Section 2.3.A.1 with the following:
2.3 —Asphalt:
A. Material to meet requirements of Section 805 —Asphalt
1. Asphalt shall be PG 58-28 and conform to Section 702 of Idaho Highway Transportation
Department Standard Specifications for Highway Construction and conform to ISPWC
Section 805.
Add Section 2.9 as follows:
2.9 - Detectable Warning Domes:
A. Detectable Warning Domes used in asphalt pavement pathways shall be constructed of a
prefabricated composite material. Metal, rubber, or ceramic detectable warning dome
materials are not permitted. Detectable warning domes shall be yellow in color unless
approved otherwise by the City. Cast iron detectable warning domes panels may be used in
specific areas following approval by the City.
48
Detectable Warning Domes shall meet the requirements of the current version of the Public
Right of Way Access Guidelines (PROWAG).
Detectable Warning Domes shall extend the full width of the ADA -accessible route (throat
width of pedestrian ramp or full width of the pedestrian access route).
49
Division 900 — Pressure Irrigation
General Information:
Requirement:
A. All developments with appurtenant agricultural water rights shall be required to construct a
secondary pressure irrigation system. If the irrigation system will be dedicated to the City, it
shall be designed and constructed to the standards of this section to utilize the water rights
for the development. Such secondary pressure irrigation systems will be dedicated to and
accepted by the City as a utility and the City will assume ownership and operation of the
system. Dedicated secondary irrigation systems shall be designed and constructed in
accordance with these standards and the current edition of the City of Chubbuck - Pressure
Irrigation Design Specification Manual.
Pressure Irrigation Pipe:
A. All such pressure irrigation pipe extensions and installations shall be in dedicated public
right of way areas and shall extend the full length of the frontage of the property being
served unless determined to be unnecessary by the City.
B. Sizing:
In areas with new development, the City of Chubbuck shall require a hydraulic analysis to
verify adequate system pressure and flows. If a proposed pressure irrigation system will be
a part of a larger phased development, it is required that the larger development be
considered in the hydraulic evaluation. A hydraulic analysis that includes a larger
development may be satisfactory to meet the hydraulic analysis requirement for a multi-
phase development.
Hydraulic model boundary conditions including irrigation water supply and flow controls
shall be clearly defined. Summary of design criteria used, including water demands, peaking
factors, pipe roughness, etc. should be included.
Pressure irrigation pipe shall be sized to meet or exceed the minimum sizes demonstrated in
the hydraulic analysis.
The pressure irrigation system shall be designed in accordance with the current edition of
the City of Chubbuck - Pressure Irrigation Design Specification Manual.
50
C. Inside Easements:
The City of Chubbuck may require or allow pressure irrigation pipe to be installed in utility
easements if it is deemed necessary for the good of the pressure irrigation system.
Depending upon site specific conditions, pressure irrigation pipe located in an easement
outside of road right-of-way may be required to be fused HDPE pipe as determined by the
City Engineer.
Access to all pressure irrigation structures shall be provided by easements of no less than
twenty feet (20') in width, centered over the irrigation structure to maintain ten feet (10')
from the easement sideline. Greater easement width may be required in special
circumstances.
D. Pipe Cover:
The top of pipe to finish grade for all pressure irrigation pipe and irrigation service lines
shall be a maximum of four feet (4') and minimum two and half feet (2.5'). In some special
cases, with the approval of the City Engineer, the pressure irrigation pipe may be installed
deeper below other utilities or at areas where air entrapment might otherwise occur, given
the extents of the pipe greater than four feet (4') deep is minimized and appropriate drains
are provided.
E. Mainline Coupling:
Mainline couplings should be used to a minimum, and only following approval of the City
Engineer or Water Superintendent.
Pressure Irrigation Valves:
A. All pressure irrigation mainline valves and fittings located near other fittings shall be
required to be flanged.
B. Location:
Pressure irrigation mainline valves shall be installed on all directions of the pressure
irrigation pipe including all crosses or tees unless otherwise approved by the City.
C. Spacing:
The maximum distance between pressure irrigation mainline valves shall be fifteen
hundred feet (1500') as measured following the distribution irrigation pipe.
D. Air entrapment:
At all high points in the pressure irrigation pipe where air entrapment is likely to occur,
51
combination air release / air vacuum valves shall be required. Valve sizing calculations shall
be provided by the design engineer, and the size and model indicated on the construction
plans. Adequate space shall be provided inside a standard manhole to allow for easy
access and maintenance. The size and height of all fittings shall be verified.
Pressure Irrigation Drain:
A. An irrigation drain shall be required at all low points in the pressure irrigation system and
at regular spacing to allow the irrigation system to completely drain. The drain and all its
appurtenances shall be constructed in accordance with manufacturer's recommendations
and City of Chubbuck Standard Drawing CSD -902 (Pressure Irrigation Drain).
B. Spacing:
The maximum distance between irrigation drains shall be eight hundred feet (800') as
measured following the distribution irrigation pipe.
Pressure Irrigation Service:
A. Location:
Upon designing the subdivision, the City of Chubbuck recommends the developer or home
builder determine the ideal location of the irrigation service box for each subdivision lot
prior to installation. The location should be along the street frontage in future landscape
areas within the utility easement, outside the driveway, and readily accessible to the
homeowner and City of Chubbuck.
After the irrigation service box is in place, if it is determined to be in an undesirable
location, the contractor or homeowner may relocate the irrigation service box, following
City approval, without disconnecting irrigation fittings or cutting the irrigation service line.
Relocation will be allowed if it is possible to swing the irrigation service box and fittings,
remaining intact, one direction or other to remain behind the sidewalk. Splices or junctions
in the service pipe between the mainline and the service box are not allowed. Prior to
relocation, the contractor or homeowner shall notify the City's public infrastructure
inspector.
B. Maintenance:
The City of Chubbuck owns and the Public Works Department shall maintain all completed
pressure irrigation service lines after installation from the point of connection at the
irrigation main through the irrigation service box in cases where the irrigation service box
is set at the nearest property line abutting the pressure irrigation main, or to the nearest
property line abutting the main in cases where the irrigation service box is otherwise not
adjacent to the nearest property line abutting the main.
52
C. Repairs:
If repairs or replacement of any irrigation service line or irrigation service box is rendered
necessary by the act, neglect, or carelessness of the owner or occupant of the premises,
any expense incurred by the City of Chubbuck for the repair or replacement shall be
charged against and collected from the property owner.
Backflow Prevention Device:
A. Requirement:
Any physical arrangement whereby a potable (domestic) water supply is connected,
directly or indirectly, with the pressurized irrigation system shall require a backflow
prevention device at the expense of the contractor or property owner.
B. Installation:
The backflow prevention device and appurtenances shall be installed in accordance with
manufacturer's recommendations and City of Chubbuck Standard Drawing CSD -903 (1"
Backflow Prevention Device).
C. Testing:
Testing and maintenance of the backflow prevention device shall be the responsibility of
the property owner. Backflow prevention devices installed pursuant to this chapter, except
atmospheric vacuum breakers, shall be inspected and tested annually, or more often if
deemed necessary by the City Engineer. Inspections, tests and maintenance shall be
conducted at the property owner's expense. Whenever the devices are found to be
defective, they shall be repaired, overhauled, or replaced at the owner's
expense. Inspections, tests, repairs and records thereof shall be accomplished by certified
testers and written test reports forwarded to the City Engineer.
D. City Code:
Refer to City Code 13.08.120 and 13.12 for the City's complete Cross Connection Control
requirements and codes.
Section 901— Pressure Irrigation Pipe and Fittings:
Rer lace Section 2.2.A.1 with the followi
2.2 — Polyvinyl Chloride (PVC) Pipe and Fittings:
A. PVC Pressure -Rated Pipe: ASTM D 2241
53
1. Pressure Class: 200 PSI (DR -21) minimum
Add Section 2.2.A.6 as follows:
6. Color: Purple
Replace Section 2.2.13 with the following:
B. PVC Pressure Pipe Sizes 4 inch through 36 inch for Irrigation:
ANSI/AWWA C 900-16
1. Pressure Class: 200 PSI (DR -21) minimum
2. Outside Diameter Basis: Cast Iron (CI) pipe equivalent
3. Joints: Bell and spigot end with ASTM F 477 elastomeric gaskets
4. Color: Purple
Remove Section 2.2.C.2 in its entirety:
Replace Sections 2.11 and 2.12 with the following:
2.11— Locate Wire:
A. Type: (No 12 AWG) single strand 12 -gauge copper clad steel (CCS) wire with purple high
density polyethylene (HDPE) insulated jacket coating for direct bury.
B. Splicing: 3M DBR direct bury splice kit or City approved equivalent and shall be watertight
to provide electrical continuity.
2.12 — Warning Tape:
A. Type: 6" wide metallic warning tape, purple polyethylene vinyl labelled "NON -POTABLE
WATER" or "IRRIGATION WATER".
Add Section 2.13 and 2.14 as follows:
2.13 — Mechanical Restraint:
A. Type: Standard mechanical joint restraint gland, restraint devices for MJ fittings and
appurtenances to conform to ANSI/AWWA C 111/A21.11 or ANSI/AWWA C 153/A21.53.
B. Product: EBAA iron series 2000 PV (PVC Pipe) or EBAA Iron Series 1100 Megalug (Ductile
Iron Pipe) or approved substitution, and to meet requirements of ASTM F 1674. An
identification number consisting of year/day/plant/shift to be cast into each gland body
from which to trace test results.
C. Application: Approved for above -grade installation. All mechanical joint fittings below grade
shall be mechanically restrained using mechanical restraints meeting the requirements of
ISPWC Section 401.2.9. Mechanical restraints shall be in addition to thrust blocks.
2.14 — Mainline Tapping Saddle:
A. Tapping saddle shall conform to AWWA C223.
54
B. Pressure Class: Minimum 175 psi
C. Connection: Flange
D. Manufacturer and Model: Romac SST, Mueller H304, or Ford FAST
Replace Section 3.2.0 with the following:
3.2 — Pipe Installation:
O. Locate wire shall be secured to the crown of the pipe with suitable tape every 8 to 10 feet
along the buried pressure irrigation pipe.
Add Sections 3.2.R and 3.2.S as follows:
R. Install 6" wide metallic warning tape, purple polyethylene vinyl labelled "NON -POTABLE
WATER" or "IRRIGATION WATER"6" to 12" below road base.
S. Where fittings are located adjacent to other fittings, all fittings shall have flanged
connections between fittings.
Add Section 3.6.0 as follows:
3.6 — Pressure Testing:
C. Once the pressure test has passed and is acceptable to City of Chubbuck, it will be the
contractor's responsibility to drain water from the pressure irrigation system. The
contractor shall open all applicable irrigation branch valves, drain valves, and ball valves
inside the irrigation service boxes. The City of Chubbuck may require the contractor to
effectively clear out the pressure irrigation system of lingering water with a sufficient air
compressor, to be observed by the City's Water Department personnel.
Replace Section 3.7 with the following:
3.7 — Locate Wire:
A. Locate wire shall be secured with suitable tape every 8 to 10 feet along the buried pressure
irrigation pipe. The locate wire shall interconnect to the locate wire of each irrigation
service line with 3M DBR direct bury splice kit or City approved equivalent and shall be
watertight to provide electrical continuity.
Locate wire shall be tested for continuity prior to road subgrade preparation. Any wire
found not to be continuous after testing shall be repaired or replaced to City satisfaction
by the contractor prior to roadway construction.
Replace Section 3.8.A with the following:
3.8 — Pipe Markers:
A. Install 6" wide metallic warning tape, purple polyethylene vinyl labelled "NON -POTABLE
WATER" or "IRRIGATION WATER" 6" to 12" below road base.
55
Add Section 3.10.D as follows:
3.10 — Connections to Existing Pressure Irrigation Mains:
D. For connections to existing pressure irrigation mains or stubs, the City will require, when
applicable, the removal of the existing irrigation pipe up to the nearest bell or spigot,
starting the new pipe installation at that location.
Add Sections 3.12 and 3.13 as follows:
3.12 — Mechanical Joint Fittings:
A. All mechanical joint fittings below grade shall be mechanically restrained using mechanical
restraints meeting the requirements of ISPWC Section 401.2.9. Mechanical restraints shall
be in addition to thrust blocks.
3.13 — Mainline Tapping:
A. For live taps onto a charged portion of the city's pressure irrigation system, all materials
will be provided and installed by the contractor or customer and the tapping will be
performed by City of Chubbuck staff. In no case shall a non -City of Chubbuck personnel
operate any part of the city's pressure irrigation system without prior written
authorization of the City Engineer or Water Superintendent.
B. When a new pressure irrigation connection is required for a new development, etc. the
contractor will be required to excavate around the existing pressure irrigation pipe and the
trench shall be sufficient to allow the city's tapping crew enough space at each location to
safely make the tap without any additional excavation. The adequacy and safety of the
excavation shall be at the sole discretion of the city's tapping crew. If the city's tapping
crew determines that any excavation does not meet City standards, the crew shall have
the option to refuse to make the tap and will reschedule at least 2 days hence.
C. The contractor shall provide all needed materials to make the connection to the existing
pressurized irrigation system and the City of Chubbuck shall preform the tap connection
for all new pressure irrigation pipe of twelve inches (12") or less. Live tap connections for
all pressure irrigation pipe larger than twelve inches (12") shall require third party
contractor. This connection will be at the expense of the developer or contractor and must
be observed and inspected by the city's water department personnel.
Section 902 — Pressure Irrigation Valves:
Add Sections 2.1.D through 2.1.G as follows:
2.1—Valve Size, Type, and Strength:
D. Gate valves are required for pressure irrigation pipe less than 12 inches in diameter.
E. Butterfly valves are required for pressure irrigation pipe of 12 inches in diameter or larger.
56
F. If system pressures are expected to exceed 100 psi, a valve rated with a working pressure
equal to or greater than the test pressure shall be required.
G. Under special circumstances a 12 -inch gate valve may replace the butterfly valve, under
approval of City Engineer.
Reolace Section 2.2.A.8 with the followi
2.2 — Resilient Seated Gate Valves:
A. Resilient Seated Gate Valves and Reduced Wall Resilient Seated Gate Valves for Water
Supply Service: ANSI/AWWA C 509 and/or ANSI/AWWA C 515 (ductile iron only):
8. Manufacturer: Kennedy Valve Co., Mueller, Clow Valve Co., or City approved
equivalent.
Replace Section 2.3.A.10 with the following:
2.3 — Butterfly Valves:
A. Rubber Seated Butterfly Valves: ANSI/AWWA C 504
10. Manufacturer: Kennedy Valve Co., Mueller, Clow Valve Co., or City approved
equivalent.
Add Section 2.4.A.5 as follows:
2.4 —Air Release, Air/Vacuum and Combination Air Valves:
A. Air Release/Air Vacuum and Combination Air Valves: ANSI/AWWA C 512.
5. Manufacture and Model: Val -Matic 800 Series Single Body Wastewater Combination
Valve 80xA or DeZURIK/APCO series 440 SCAV Single Body Sewage Combination Valve
or City approved equivalent.
Replace Section 2.6 with the followi
2.6 —Valve Boxes:
A. Paved or Traffic Areas:
1. Valve boxes in accordance with ISPWC Section 401 and City of Chubbuck Standard
Drawing CSD -405 (Valve Box and Lid)
B. Non -Traffic Areas:
1. Valve boxes in accordance with ISPWC Section 401 and City of Chubbuck Standard
Drawing CSD -405 (Valve Box and Lid), however concrete collars not required.
57
Replace Sections 3.2.A and 3.2.13 with the following:
3.2 — Installation:
A. Install valves and appurtenances in accordance with manufacturer's recommendations and
City of Chubbuck Standard Drawings.
B. Install valves plumb and vertical. Set valve box centered and plumb over wrench nut and
flush with ground or street surface. Install box per City of Chubbuck Standard Drawing
CSD -405 (Valve Box and Lid)
Section 903 — Pressure Irrigation Service Lines and Appurtenances:
Add Sections 2.1.D as follows:
2.1— Pipe and Fittings Size, Type and Strength:
D. Pipe over two inches (2") in diameter shall meet the requirements of the pressure irrigation
pipe and fittings specified in ISPWC Section 901.
Replace Section 2.2.A with the followi
2.2 — Service Pipe and Fittings:
A. Polyvinyl Chloride (PVC) Service Pipe Not Allowed
Remove Section 2.2.13.5 in its enti
Add Section 2.2.13.6 as follows:
B. Polyethylene (PE) Pressure Pipe for Water Service: ANSI/AWWA C 901
6. Color: Black or Blue with hand painted purple stripes along the length of the service
pipe.
Replace Section 2.3.A with the following:
2.3 —Appurtenances:
A. Service Saddles for PVC Main:
1. Service line fittings (service saddle, corporation stop, etc.) shall be manufactured by
Ford or Romac as detailed in the City of Chubbuck Standard Drawings .
2. All service saddles shall include double strap stainless steel bands. Saddle bodies shall
be iron or brass. Iron saddles bodies shall be lined and coated with fusion -bonded
epoxy, nylon, or approved substitution. Lining or coating per manufacture's
specifications.
58
Replace Section 2.3.C.1 with the following:
C. Service Valves:
1. Type: 200 psi rated ball valves, Watts WBVC or City approved equivalent as detailed in
the City of Chubbuck Standard Drawings CSD -901 (1" Pressure Irrigation Service).
Remove Section 2.3.C.4 in its entirety:
Replace Section 2.3.E with the following:
E. Irrigation Service Box:
1. Size and Type:
For landscape areas, the irrigation service box shall be 18" x 24" Fiberglass Vault with Lid
marked "Irrigation", Carson 12201014 or City approved equivalent as detailed in the City
of Chubbuck Standard Drawings CSD -901 (1" Pressure Irrigation Service).
For driveway areas, the irrigation service box shall be a minimum size of 24" x 24" inside
dimensions and shall meet ANSI/SCTE 77—TIER 15 load requirements (15,000 LBS).
Before the driveway is poured, an additional 2" minimum diameter sleeve shall be
installed below the driveway from the irrigation service box to the landscape area.
2. Marking Tag: Inside the irrigation service box, there shall be two (2) plastic tags at 10 mil
minimum thickness with a metal grommet, securely fastened by the contractor to the
ball valves or fittings. The first tag shall be supplied by the City and clearly marked
"Property of City of Chubbuck, DO NOT MODIFY". The second tag shall be supplied by
the contractor and be purple and clearly marked "Non -Potable Water, DO NOT DRINK".
Add Sections 2.3.F and 2.3.G as follows:
F. Corporation Stops:
1. Product: Ford F1001 -4 -G -NL with CC threads
G. Locate Wire:
1. Type: (No 12 AWG) single strand 12 gauge copper clad steel (CCS) wire with purple high
density polyethylene (HDPE) insulated jacket coating for direct bury.
Replace Section 3.2.A with the following:
3.2 — Installation:
A. Install irrigation service line, fittings, and irrigation service box in accordance with the
manufacturer's recommendations and City of Chubbuck Standard Drawing CSD -901 (1"
Pressure Irrigation Service).
59
Add Sections 3.21 and 3.2.M as follows:
L. Locate wire shall be secured with suitable tape every 8 to 10 feet along the buried
irrigation service pipe. Locate wire shall interconnect to the locate wire of the pressure
irrigation main with 3M DBR direct bury splice kit or City approved equivalent and shall be
watertight to provide electrical continuity.
Locate wire shall be minimum of 24" of excess wire beyond the ball valve as shown on the
City of Chubbuck Standard Drawings CSD -901 (1" Pressure Irrigation Service).
M. When irrigation service lines are required to be abandoned, the pressurized irrigation
service pipe shall be disconnected at the point of connection to the pressure irrigation
main and shall be plugged with a brass plug. The City shall witness that no leaks occur prior
to any placement of bedding material.
Add Section 3.4 as follows:
3.4 —Mechanical Restraint:
Application: All mechanical joint valves below grade shall be mechanically restrained using
mechanical restraints meeting the requirements of ISPWC Section 401.2.9. Mechanical
restraints shall be in addition to thrust blocks.
.0
Division 900 — Pressure Irrigation
City of Chubbuck Standard Drawings
CSD -901 1" Pressure Irrigation Service
CSD -902 Pressure Irrigation Drain
CSD -903 1" Backflow Prevention Device
61
(
z
Z 0 J
OU�o Z z
aZ cn�: Oo
(DZ�o� Qc N
Lu O p U Q Q Q EASEMENT LINE
j Z Y Z m
OHUZf-
wL: OO
d LL W U Z
W
w �
z Z
� ui
3: o _O
o = z_wwQ z H
>_w g U
3= ���� LU
N (n p Q c J co
r Q
H
kis
co
00 w a cD z
Z of o
M
2 0LLJ
HU
pLLZ
H
0wLL izz
Y HZ 0-0
U g w� w i z > a D U
pC7pww o z 0 }
mz���0 wc~i�0PZU)co W o
2 Q Z w M W z J L
Z of W Q Z X
U�2mZ �oWQzp� z gQ
LL. pwz-0 wP:w zZ
O p O O Q m� Z J W 2 Q J U) N
H- 0-
I-Q<O �0ma0p LL
()z <0- 0(D w
w< cl. �=w<
W Hc)WO NUcnO��� Lo
cn U) U)
N — ► J N
>Q
W N
0
cn
r
FOR PUBLIC
WORKS
CHUBBUCK CONSTRUCTION LAST REVISED 3/24/2026
STANDARDS 1" PRESSURE STANDARD DRAWING NO:
D R H 0 IRRIGATION SERVICE CSD -901 1 OF 2
MATERIAL LIST:
1. WATER MAIN (PVC, HDPE, OR DUCTILE IRON) PRESSURE CLASS 200 PSI (DR -21) MINIMUM, SEE MATERIAL
SPECIFICATIONS.
2. 1" CORPORATION STOP W/ CC THREADS (FORD F1001 -4 -G -NL)
3. 1" IRRIGATION SERVICE LINE (POLYETHYLENE SIDR-7, BLACK OR BLUE WITH HAND PAINTED PURPLE
STRIPES ALONG THE LENGTH OF THE SERVICE PIPE, SEE MATERIALS SPECIFICATIONS) NO SPLICES OR
FITTINGS ALLOWED BETWEEN CORPORATION STOP AND VALVE ASSEMBLY.
4. FOR LANDSCAPE AREAS THE IRRIGATION SERVICE BOX SHALL BE 18" x 24" FIBERGLASS VAULT W/ LID,
CARSON 12201014 OR CITY APPROVED EQUIVALENT.
FOR DRIVEWAY AREAS THE IRRIGATION SERVICE BOX SHALL BE A MINIMUM SIZE OF 24" x 24" INSIDE
DIMENSIONS AND SHALL MEET ANSI/SCTE 77 - TIER 15 LOAD REQUIREMENTS (15,000 LBS). BEFORE
THE DRIVEWAY IS POURED ADDITIONAL 2" MINIMUM SLEEVE SHALL BE INSTALLED BELOW THE
DRIVEWAY FROM THE IRRIGATION SERVICE BOX TO THE YARD.
5. SERVICE SADDLE FOR PVC MAIN:
8" PVC (FORD FCD202-905-TAP-CC4) OR (ROMAC 202S - 905 x 1" CC)
10" PVC (FORD FCD202-11 1 0-TAP-CC4) OR (ROMAC 202S - 1110 x 1" CC)
12" PVC (FORD FCD202-1320-TAP-CC4) OR (ROMAC 202S - 1320 x 1" CC)
6. 1" BALL VALVE (WATTS WBVC) OR APPROVED EQUIVALENT
7. 1" BRASS TEE
8. 1" BRASS 90° STREET ELBOW
9. SUPPLIED BY THE CITY, PLASTIC TAG (10 MIL MINIMUM THICKNESS) MARKED "PROPERTY OF CITY OF
CHUBBUCK, DO NOT MODIFY" SEE MATERIAL SPECIFICATIONS
10. SUPPLIED BY THE CONTRACTOR, PLASTIC TAG (10 MIL MINIMUM THICKNESS) PURPLE AND MARKED
"NON -POTABLE WATER, DO NOT DRINK" SEE MATERIAL SPECIFICATIONS
11. LOCATE WIRE (NO. 12 AWG. COPPER CLAD STEEL (CCS) W/ PURPLE INSULATED JACKET COATING)
12. LOCATE WIRE SPLICE CONNECTER (3M DBR DIRECT BURY SPLICE KIT) SEE MATERIAL SPECIFICATIONS
13. 1" PIPE NIPPLE (4" IN LENGTH)
14. 1" PIPE NIPPLE (2" IN LENGTH)
15. TYPE I PIPE BEDDING PER SECTION -305 OF ISPWC
16. 1" STAINLESS STEEL OR BRASS UNION WITH (2) 1" PIPE NIPPLES (1" IN LENGTH) EACH SIDE
NOTES:
A. CUL-DE-SAC IRRIGATION SERVICE LATERALS MUST FOLLOW THE MOST DIRECT ROUTE POSSIBLE
BETWEEN CORPORATION STOP AND IRRIGATION SERVICE BOX.
B. IRRIGATION SERVICE LINE CONNECTION MUST BE A MIN. OF 2 FT. BEHIND EASEMENT LINE.
C. ALL CONSTRUCTION SHALL CONFORM TO THE REQUIREMENTS OF THE CITY OF CHUBBUCK AND THE
IDAHO STANDARDS FOR PUBLIC WORKS CONSTRUCTION.
D. PRIOR TO BACKFILLING THE CITY OF CHUBBUCK SHALL INSPECT INSTALLATION OF THE PRESSURE
IRRIGATION PIPE, IRRIGATION SERVICE LINE, AND IRRIGATION SERVICE BOX.
E. WHEN USING ROADSIDE DRAINAGE SWALE TYPICAL STREET SECTION SET TOP OF METER BOX 3" TO 4"
ABOVE TOP BACK OF CURB.
F. ALL FITTING SHALL BE BRASS COMPRESSION WITH INSERTS.
CHUBBUCK
IDDH0
FOR PUBLIC
WORKS
CONSTRUCTION
LAST REVISED 3/24/2026
STANDARDS 1 1" PRESSURE STANDARD DRAWING NO:
IRRIGATION SERVICE I CSD -901 2 OF 2
Q
O
ry
- / I -44�4 c N —
CHUBBUCK
I D R H 0
FOR PUBLIC
WORKS
CONSTRUCTION
STANDARDS
PRESSURE
IRRIGATION DRAIN
LAST REVISED 3/24/2026
STANDARD DRAWING NO:
CSD -902 1 OF 2
MATERIAL LIST:
1. TEE (FLG X MJ)
2. GATE VALVE (FLG X MJ)
3. CONCRETE THRUST BLOCK PER ISPWC SPECIFICATIONS
4. 2 CY OF 3" WASHED DRAIN ROCK
5. NONWOVEN FILTER FABRIC AROUND DRAIN ROCK, 1' OVERLAP MIN.
6. TYPE I BEDDING PER SECTION 305 OF ISPWC
7. CAST IRON VALVE BOX (SEE CITY OF CHUBBUCK STANDARD DRAWING CSD -405)
8. IRRIGATION DRAIN LATERAL TO BE SAME DIAMETER
OF PIPE AS MAINLINE (DUCTILE IRON OR PVC)
9. LOCATE WIRE (NO. 12 AWG. COPPER CLAD STEEL (CCS) W/ PURPLE INSULATED JACKET
COATING)
10. LOCATE WIRE SPLICE CONNECTER (3M DBR DIRECT BURY SPLICE KIT) SEE MATERIAL
SPECIFICATIONS
11. MECHANICAL RESTRAINT IN ADDITION TO THRUST BLOCKS
NOTES:
A. DRAIN SHALL BE LOCATED AT ALL LOW SPOTS ALONG THE PRESSURE IRRIGATION
SYSTEM.
B. THE END OF THE IRRIGATION DRAIN LATERAL SHALL BE CENTERED BELOW THE
ROADSIDE DRAINAGE SWALE.
CHUBBUCK
IDDH0
FOR PUBLIC
WORKS
CONSTRUCTION
STANDARDS
LAST REVISED 3/24/2026
PRESSURE STANDARD DRAWING NO:
IRRIGATION DRAIN I CSD -902 2 OF 2
Z_
Lu Q
LLI Lu DZ
Q 000 w0
w~ Z
Q
QQn
U UHZ J O�
Q —
Z ti Q r`
O
qO
LC w (N
co Q %
Z Z
_O
X Y o
U Lu m 0 �
In w m (n
U U
o > = O
o Lo W U Z
Z ° z U Q
co i Q X o 0
O ~
D g m Q U
} YY U) U
C) L) u1UU W Q
F-- m U 0
2i m z Q
co J]fD§
w=Q U)
QLo
foo
-i�Q
mCJ�
H w Q
M Owl-
0- cf) U)
Li
cr
w
Q
�i w
w In JZ
Q
<0 Q
�= OLu
Lu 0
�w
Q
<~ o�
O
a_
FOR PUBLIC
WORKS
CHUBBUCKCONSTRUCTION LAST REVISED 3/24/2026
STANDARDS 1" BACKFLOW STANDARD DRAWING NO:
I D D H 0 PREVENTION DEVICE CSD -903 1 OF 2
CHUBBUCK
IDDH0
MATERIAL LIST:
1. 1" POTABLE WATER SERVICE LINE (POLYETHYLENE)
2. 1" IRRIGATION SERVICE LINE (POLYETHYLENE)
3. PVC VALVE SLEEVE W/ CAP
4. 1" BRASS STOP AND WASTE VALVE
5. 1" REDUCED PRESSURE PRINCIPAL BACKFLOW
PREVENTION DEVICE (RP), TO BE TESTED ANNUALLY
MAKE MODEL
WATTS RK009M2
ZURN WILKINS 1-375
FEBCO LF860
OR APPROVED DEVICE OR ASSEMBLY LISTED ON
FOUNDATION FOR CROSS CONNECTION CONTROL HYDRAULIC
RESEARCH
6. 1" BRASS 90° ELBOW W/ COMPRESSION FITTINGS
7. 1" BRASS TEE W/ COMPRESSION FITTINGS.
NOTES:
A. THIS TYPE OF INSTALLATION IS ONLY REQUIRED WHEN
CROSS CONNECTION IS TAKING PLACE BETWEEN THE
POTABLE AND NON POTABLE WATER.
B. THE BACKFLOW PREVENTION DEVICE SHALL BE THE
EXPENSE AND RESPONSIBILITY OF THE WATER USER TO
HAVE A CERTIFIED INSPECTION AND OPERATIONAL TEST
AT LEAST ONCE A YEAR.
C. TO PROTECT THE BACKFLOW PREVENTION DEVICE AND
APPURTENANCES FROM WATER FREEZING IN WINTER
CONDITIONS TO CLOSE THE STOP AND WASTE VALVE AND
EFFECTIVELY CLEAR OUT THE PRESSURE IRRIGATION
SYSTEM OF LINGERING WATER.
FOR PUBLIC
WORKS
CONSTRUCTION
STANDARDS
1" BACKFLOW
PREVENTION DEVICE
LAST REVISED 3/24/2026
STANDARD DRAWING NO:
CSD -903 2 OF 2
Division 1100 —Traffic
Section 1102 — Street Lighting:
Replace Section 2.10.0 with the following:
2.10 — Metal Poles:
C. Install metal pole with a concrete base following City of Chubbuck Standard Drawing CSD -
1101 (Street Light Installation) and ISPWC Standard Drawing SD -1109 (Standard Signal Pole
Foundation Detail).
Replace Section 2.11 with the following:
2.11— Fiberglass Poles Not Allowed
Replace Section 2.13.A with the following:
2.13 — Concrete Pole Bases:
A. Concrete to be Class 4000 psi meeting the requirements of ISPWC Section 703 — Cast -in -
Place Concrete.
Replace Section 3.2.A with the followi
3.2 —Junction Box Installation:
A. Install to locations as shown on the plans and at the power source following City of
Chubbuck Standard Drawing CSD -1101 (Street Light Installation). If not shown, space
equidistant not to exceed 400 feet along straight conduit runs occur, at sharp bends, wire
splices, or where direct burial and conduit junctions occur. Between junction boxes that
are spaced beyond 200 feet, a minimum of 1-1/2" diameter conduit shall be used.
Replace Section 3.8.F with the following:
3.8 — Concrete Pole Bases:
F. Base dimensions and installation details shall conform to City of Chubbuck Standard
Drawing CSD -1101 (Street Light Installation) and ISPWC Standard Drawings SD -1109 and
SD -1116.
Replace Section 3.9.13 with the following:
3.9 — Pole Installation:
B. Install wood poles in accordance with ISPWC Standard Drawing SD -1118. Install metal
poles in accordance with City of Chubbuck Standard Drawing CSD -1101 (Street Light
Installation) and ISPWC Standard Drawings SD -1109 and SD -1116.
Section 1105 — Permanent Traffic Signing:
Add Section 2.2.E as follows:
2.2 — Signs:
E. Street Name Signs to follow layout and sizing as shown on City of Chubbuck Standard Drawing
CSD -1102 (Street Name Sign).
Division 1100 —Traffic
City of Chubbuck Standard Drawings
CSD -1101 Street Light Installation
CSD -1102 Street Name Sign
70
1 of
FUSED "IN-LINE" TYPE WIRE CONNECTOR
ninTc:c• SET SCREW TYPE ONLY
A. THE CONTRACTOR SHALL VERIFY LINE VOLTAGE
PRIOR TO CONNECTING WIRE CONNECTORS.
B. CONTRACTOR SHALL CONNECT CONDUCTOR
FROM THE WIRE CONNECTOR TO NEW
LUMINAIRE WITH A NO. 10 AWG. TYPE THW. 600V
INSULATED WIRE.
C. FOR CONCRETE BASE DETAILS SEE IDAHO
STANDARDS FOR PUBLIC WORKS
CONSTRUCTION (ISPWC) STANDARD DRAWING
SD -1109.
D. GROUND ROD MAY BE PLACED IN LIEU OF
CONNECTION TO REBAR CAGE.
E. 1-1/2" CONDUIT IS REQUIRED WHEN THE
DISTANCE BETWEEN JUNCTION BOXES ARE
200 FEET OR GREATER.
INSTALL JUNCTION BOX,
NEW BASIS PCA 173018 (OR
APPROVED EQUIVALENT)
TO BE SET WITHIN 3 FEET
OF POWER COMPANY
J -BOX OR TRANSFORMER.
POWERFUSED
COMPANY J -BOX
J -BOX OR
ANSFORM R
NEC CODE
APPROVED -
CONNECTOR
HAND HOLE -
NEC CODE
APPROVED
GROUNDING
CONNECTOR
0
Z
INSTALL FUSE: FAST
ACTING -100K RMS
MIN. 1" CONDUIT
AMPS-600VAC SEC D
¢
0w
0
MODEL 1791 -DF OR SEC
z
w
O
MODEL 1791 -SF (OR
2i
d U
APPROVED EQUIVALENT).
Lu W
�0z
NEC CODE.
JUNCTION T
BOX
/ I - 64 �(t CA -
CHUBBUCK
I D R H 0
FOR PUBLIC
WORKS
CONSTRUCTION
STANDARDS
LED LUMINAIRE
PHOTO CELL (TWIST LOCK
TYPE) MARK P.E. CONTROL &
LAMPS WITH INSTALLATION
DATE.
INSTALL FUSE: FAST
ACTING -100K RMS
AMPS-600VAC SEC
MODEL 1791 -DF OR SEC
MODEL 1791 -SF 1791 -SF
(OR APPROVED
EQUIVALENT).
#10 MIN. WIRES
FROM FUSE
CONNECTOR TO
FIXTURE.
#6 MIN. WIRES
FROM POWER
SOURCE TO FUSE
CONNECTOR.
CONDUIT & WIRING
MIN. 1" CONDUIT
TO NEXT STREET
(SCHEDULE 40 PVC UL�
LIGHT IN SYSTEM
APPROVED) SIZE MY
VARY PER NEC CODE,
NOTES:
WIRE COLORS PER
ADDITIONAL J -BOX (PULL BOX) IS
NEC CODE.
I REQUIRED WHEN THE DISTANCE
BETWEEN THE STREET LIGHT
GROUND ROD (PER
AND FUSED JUNCTION BOX IS 50
NEC ARTICLE
j FEET OR GREATER.
250 -GROUNDING
— WHEN SPLICE REQUIRED USE
BONDING PER NEC
I SEC MODEL 0791-0 SPLICE KIT,
ARTICLE 230 -SERVICE).
OR APPROVED EQUIVALENT
/ I - 64 �(t CA -
CHUBBUCK
I D R H 0
FOR PUBLIC
WORKS
CONSTRUCTION
STANDARDS
LED LUMINAIRE
PHOTO CELL (TWIST LOCK
TYPE) MARK P.E. CONTROL &
LAMPS WITH INSTALLATION
DATE.
INSTALL FUSE: FAST
ACTING -100K RMS
AMPS-600VAC SEC
MODEL 1791 -DF OR SEC
MODEL 1791 -SF 1791 -SF
(OR APPROVED
EQUIVALENT).
#10 MIN. WIRES
FROM FUSE
CONNECTOR TO
FIXTURE.
#6 MIN. WIRES
FROM POWER
SOURCE TO FUSE
CONNECTOR.
HEIGHT 4" TO 6"
1/2" X 6" P.V.C.
CONDUIT SLEEVE
FILL TOP 2" WITH
SILICONE GROUT.
�\
HEIGHT 4" TO 6"
1/2" X 6" P.V.C.
CONDUIT SLEEVE
FILL TOP 2" WITH
SILICONE GROUT.
NEC CODE APPROVED
GROUNDING
CONNECTOR
STREET LIGHT
INSTALLATION
4000 PSI
CONCRETE
LAST REVISED 3/24/2026
STANDARD DRAWING NO:
CSD -1101 1 OF 1
1" CONDUIT
° 4'
(SCHEDULE 40 PVC
UL APPROVED)
USED AS SLEEVE
a
FOR DRIP TUBING
TO ABOVE HANGING
a
a
PLANTER.
DIRECTION OF
CONDUIT TO BE
ACCESSIBLE, NOT
BELOW HARD
SURFACE SUCH AS
SIDEWALK.
NEC CODE APPROVED
GROUNDING
CONNECTOR
STREET LIGHT
INSTALLATION
4000 PSI
CONCRETE
LAST REVISED 3/24/2026
STANDARD DRAWING NO:
CSD -1101 1 OF 1
in
N
/ l! )
N
u ,
---
U
U H H
>-
0
OU
Q }
m —i Lij
} Lu T -
= H
LLm F-
a
=z
Lu
w�
>
��
F-
>_
LU
J
F- 0
w
w
LU Z
LU
LL
O}
Q
LLJ
F O
m
0
Oz
uJ
W
U
U
O c/)Lu
_
Z
U
2
cA
W U
=
U)
LL_
J
0.
H
z
Q
D Lu
O
�M
QLL
Lu
z LLJ
Li
O
Lu
O
=
U)
= Lu
~
0Lu
=
< of
0
0 U)
� LL
cf)0
� 0
Q U
W Y
QQ
0
Lu
Q w
��z
0�
pW
W
N D
co
Lu
in o
LL_ m
z
LLJ 0 O_
LL 2
z
U
J O
J LL
0
J O
J
O_
z
F- 0- Q
J--
m~
Q a
O
w_
=
= Y
U O
>
cn�
cn<
-jo
pv0
U)0
zz
UY
z00
()0
LU Li
��
F~z
=� J
z
CDw
cn
Z
U)U
(nom
0Z
UJQ
cnQ�
F-
LU
W?
Qw LLJ
=0Z
Lu F-
O
Q 2
Q 0
J D
Z L H
Q Y
z
z
z
Q0
wHg
W Z
H�
W W
W U
pip
= Q Q
H=
W m
CD
�
o
0�
T�
�F-
Cl) ()f
�_
lif
Z
U) Q
U)�
2�
< LL
U U
OLLC)
Q
o0
U
6
u1
u
i
O
Z
D
O
C�
Y
U
Q
m
Z
W
W
CO
FOR PUBLIC
WORKS
°D
LAST REVISED 3/24/2026
CHUBBUCK
CONSTRUCTION
NAME
STANDARD
DRAWING NO:
STANDARDS STREET
D R H 0
SIGN
CSD -1102 1 OF 1
Division 2000 — Miscellaneous
Add the following to Division 2000:
Section 2060 — Neighborhood Mailbox:
A. Requirement:
The developer shall provide for the installation of consolidated mailboxes, generally
described by the United States Postal Service as a Cluster Box Unit (CBU), which shall service
homes within the proposed subdivision. For the developments of less than (4) four homes,
the developer shall endeavor to cooperate with adjoining landowners for the installation of
such a CBU system. Upon application to the City Engineer, the requirement for a CBU in a
new subdivision may be waived for cause, such as impracticality due to the circumstances of
the development or area.
B. Sizing:
Cluster Box Unit (CBU) shall include (1) one incoming mailbox compartment for each
dwelling unit with (1) one outgoing mail slot. There must be at least (1) one parcel locker for
every (12) twelve dwelling units. No maximum number of parcel lockers to be installed.
C. Location:
The Cluster Box Unit (CBU) shall be centrally located in the development, adjacent to the
city sidewalk, so that customers are not required to travel an unreasonable distance to
obtain their mail and so there is sufficient access to mailbox locations with adequate space
for carriers to deliver and customers to retrieve the mail. Typically, a CBU shall be located
no more than 300 feet walking distance from the residence. If the CBU is located
midblock, it shall be centered near a common lot line.
D. Installation:
Install Cluster Box Unit (CBU) in accordance with manufacturer's recommendations and
City of Chubbuck Standard Drawing CSD -2001 (Neighborhood Mailbox).
E. Accessibility:
CBU's must be ADA accessible from the sidewalk and from the street. If the CBU is located
on private property or on a commonly owned lot, the established Homeowners
Association (HOA) or property owner must ensure that access is kept reasonably clear of
snow, weeds, and other obstructions. If the CBU is located within the public right-of-way,
73
the adjacent property owner must ensure the access is kept reasonably clear of snow,
weeds, and other obstructions.
Section 2070 — Garbage Dumpster Enclosure:
A. Garbage dumpster enclosures shall be privately owned and maintained by the property
owner or homeowner association. If the enclosure includes gates, the gates shall have the
ability to be fixed, or pinned, in a 120 -degree open position. Gates shall be operated by the
customer.
B. Sizing:
For multiple dwelling units that utilize commercial style containers/dumpsters and garbage
dumpster enclosure(s), the number of containers will be determined as follows:
For residential use, each dwelling unit is estimated to generate 0.6 cubic yard of solid
waste weekly. The largest container/dumpster shall be a six-yard container with a
maximum dump frequency of three times a week. The resulting number of containers shall
be rounded up to the next whole number.
Example of a 40 -unit complex:
40 units x 0.6 CY = 24 CY of solid waste generated weekly
24 CY/ 6 CY dumpster/3 dumps per week = 1.33 or 2 containers minimum
The City will consider requests from the developer or customer to utilize alternate sizing
calculations given that the developer or customer provides supporting justification. The
developer or customer may choose to increase the number of containers if desired as long
as sufficient enclosures are provided.
The size and number of enclosures shall be sufficient for the number of containers needed.
The garbage dumpster enclosure shall be enclosed on three sides and shall be no less than
six (6) feet in height. Enclosure shall have a minimum inside unobstructed width of eleven
(11) feet and minimum inside unobstructed depth of ten (10) feet in accordance with City
of Chubbuck Standard Drawing CSD -2002 (Garbage Dumpster Enclosure). Double
containers may be used side by side which shall require the minimum inside width of
twenty-two (22) feet. Additional space may be built to accommodate private recycling
container(s) which shall not encroach into said minimum width and depth clearances.
C. Location:
All garbage dumpster enclosure locations including rollout areas shall provide for direct and
unobstructed access by solid waste equipment and personnel.
74
Enclosures located on private drives must have adequate room for a sanitation truck to loop
throughout the development or turn around as shown on the City of Chubbuck Standard
Drawing CSD -2003 (Sanitation Truck Turnaround). To prevent vehicle parking in these areas,
painted pavement markings or other items may be required. The truck is approximately
33.5 feet in length and must be able to line up directly with the dumpster inside the
enclosure.
A minimum overhead height clearance of 25 feet is required to safely move containers in
and out of the enclosure. Gates in the open position shall not infringe in traffic aisles. The
City's Sanitation Department and the City Engineer shall approve all proposed enclosure
locations prior to issuance of a building permit.
75
Division 2000 — Miscellaneous
City of Chubbuck Standard Drawings
CSD -2001 Neighborhood Mailbox
CSD -2002 Garbage Dumpster Enclosure
CSD -2003 Sanitation Truck Turnaround
76
BASE & 1/2" DIA. ANCHOR BOLTS
SUPPLIED W/ UNITS AS SPECIFIED. CAST -IN-PLACE
USE TEMPLATE TO ENSURE CONCRETE BASE
ALIGNMENT OF BOLTS #4 REBAR SPACED
4" THICK CONCRETE TO 1/2" EXPANSION @ 16" O.C. EACH WAY
BE CONSTRUCTED AS BOARD 1/2" RADIUS TOOLED
PART OF MAILBOX ITEM EDGE ALL EDGES
0
4" OF 3/4" MINUS
CRUSHED BASE - _
MATERIAL AS PER q 3" CLR.
ISPWC SECTION 800 �;i (TYP.)
COMPACTED 3/4" MINUS ' T-0"
BASE MATERIAL AS PER EACH WAY UNDISTURBED NATIVE SOIL
ISPWC SECTION 800
SECTION VIEW
16 UNIT 8 UNIT
�=A
�� ELEVATION VIEW
CA
=A C C
I -I FC
CHUBBUCK
I D R H 0
MODEL #3316 TYPE III
MULTI -SIZE COMPARTMENT
CBU WITH (1) ONE OUTGOING
MAIL SLOT LOCATED IN DOOR
"B" (MANUFACTURED BY
WWW.MAILBOXES.COM OR
APPROVED EQUAL)
A: INCOMING MAIL
COMPARTMENT
B: OUTGOING MAIL SLOT
C: PARCEL LOCKER n
FOR PUBLIC
WORKS
CONSTRUCTION
STANDARDS
MODEL #3308 TYPE I
MULTI -SIZE COMPARTMENT
CBU WITH (1) ONE OUTGOING
MAIL SLOT LOCATED IN DOOR
"B" (MANUFACTURED BY
WWW.MAILBOXES.COM OR
APPROVED EQUAL)
MODEL #3312 TYPE II
MULTI -SIZE COMPARTMENT
CBU WITH (1) ONE OUTGOING
MAIL SLOT LOCATED IN DOOR
"B" (MANUFACTURED BY
SALSBURY INDUSTRIES OR
APPROVED EQUAL)
LAST REVISED 3/24/2026
NEIGHBORHOOD STANDARD DRAWING NO:
MAILBOX CSD -2001 1 OF
SIDEWALK
T-0"
12" THICK
1'-6" _ CAST -IN-PLACE
CONCRETE BASE
°
a
a
a ° -
°
N
a O
a
� + M
BROOM FINISH
+ � a
a SWALE
a
°a
J
Q Ll
C? U
w } BASE & 1/2" DIA. ANCHOR
SWALE >- 4" THICK CONCRETE TO BOLTS SUPPLIED W/ UNITS
BE CONSTRUCTED AS AS SPECIFIED. USE
PART OF MAILBOX ITEM TEMPLATE TO ENSURE
ALIGNMENT OF BOLTS
6'-0"
1/2" RADIUS TOOLED EDGE
ALL EDGES
°a
1
4 °
RIBBON CURB
PLAN VIEW
NOTES:
A. THE DOORS TO THE MAILBOX
COMPARTMENTS SHALL FACE
TOWARDS THE STREET.
FOR PUBLIC
WORKS
CHUBBUCK CONSTRUCTION LAST REVISED 3/24/2026
STANDARDS NEIGHBORHOOD STANDARD DRAWING NO:
I D R H O MAILBOX CSD -2001 2 OF 2
CL w
w p
p w
z Of
D
w o O
w z
ly- w
U w
z p
O cn
U z
12'-6" MIN. (SINGLE DUMPSTER)
25-0" MIN. (DOUBLE DUMPSTER)
(CONCRETE PAD LENGTH)
11'-0" MIN. (SINGLE DUMPSTER)
22'-0" MIN. (DOUBLE DUMPSTER)
(INSIDE ENCLOSURE LENGTH)
DESIGN CONCRETE
PAD TO WITHSTAND
10,000 LBS PER SINGLE
WHEEL LOAD
6" DIA. PIPE BOLLARD,
CONCRETE FILLED, SET 3'
BELOW GRADE, EXTEND 4'
ABOVE GRADE, PAINT OSHA
YELLOW
CONTAINER ENCLOSURE
SHALL BE 6'-0" HIGH MIN.
3/4" DIAMETER BY 1-1/2"
DEEP RECESS HOLE FOR
- CANE BOLTS. PROVIDE TWO
PER EACH GATE IN CLOSED
AND OPEN POSITION.
O O Oma,
6" DIA. PIPE BOLLARD,
z
GARBAGE
CONCRETE FILLED, SET
RECOMMENDED,
SWING
DUMPSTER
BUT OPTIONAL)
MIN.
I?
GRADE, PAINT OSHA
co
YELLOW
PLAN VIEW
* IF GATED, THE DOORS IN
DESIGN CONCRETE
PAD TO WITHSTAND
10,000 LBS PER SINGLE
WHEEL LOAD
6" DIA. PIPE BOLLARD,
CONCRETE FILLED, SET 3'
BELOW GRADE, EXTEND 4'
ABOVE GRADE, PAINT OSHA
YELLOW
CONTAINER ENCLOSURE
SHALL BE 6'-0" HIGH MIN.
3/4" DIAMETER BY 1-1/2"
DEEP RECESS HOLE FOR
- CANE BOLTS. PROVIDE TWO
PER EACH GATE IN CLOSED
AND OPEN POSITION.
/ I - 64 �(t CA -
CHUBBUCK
I D R H 0
IF GATES ARE INSTALLED, THEY
MUST BE OPENED AND SECURED
TO BOLLARDS PRIOR TO SERVICE.
THE CITY WILL NOT SERVICE THE
GARBAGE CONTAINER IF GATES
ARE NOT OPEN AND PROPERLY
SECURED.
FOR PUBLIC
WORKS
CONSTRUCTION
STANDARDS GARBAGE DUMPSTER
ENCLOSURE
LAST REVISED 3/24/2026
STANDARD DRAWING NO:
CSD -2002 1 OF 1
DOUBLE SWING
6" DIA. PIPE BOLLARD,
GATE (NOT
�120'
CONCRETE FILLED, SET
RECOMMENDED,
SWING
T BELOW GRADE,
BUT OPTIONAL)
MIN.
EXTEND 4' ABOVE
GRADE, PAINT OSHA
YELLOW
PLAN VIEW
* IF GATED, THE DOORS IN
THE OPEN POSITION
SHALL HAVE THE
ABILITY TO BE FIXED OR
PINNED TO THE PIPE
BOLLARD.
/ I - 64 �(t CA -
CHUBBUCK
I D R H 0
IF GATES ARE INSTALLED, THEY
MUST BE OPENED AND SECURED
TO BOLLARDS PRIOR TO SERVICE.
THE CITY WILL NOT SERVICE THE
GARBAGE CONTAINER IF GATES
ARE NOT OPEN AND PROPERLY
SECURED.
FOR PUBLIC
WORKS
CONSTRUCTION
STANDARDS GARBAGE DUMPSTER
ENCLOSURE
LAST REVISED 3/24/2026
STANDARD DRAWING NO:
CSD -2002 1 OF 1
REVERSE VEMENT
R2
EDGE TIRES
FpGF 50,
Ck
23.50'
FORWARD MOVEMENT
i
I �
l FOG�2.301
TURF
R 37.50' S
EDGE TIRES
I I �
IR 39 SOUGK Lo
EDC'E�R
Z_
Z
00-1
Q�
0c
O
11.25' 12.75'
24.00'
FOR PUBLIC
WORKS
CHUBBUCK CONSTRUCTION SCALE: 1" = 12'
STANDARDS SANITATION TRUCK
D R H O TURNAROUND
LAST REVISED 3/24/2026
STANDARD DRAWING NO:
CSD -20031 OF 1
Division 2100 — QC Division
Supplement the Field QC Manual with the following testing standards and frequencies. The values
in this table have precedence over the values in the ISPWC QC Field Manual.
81
Standard Method
Acceptance Criteria
Test Description
Frequency of Tests
and
(ASTM, AASHTO)
Allowable Tolerance
Moisture Density Test
ASTM D698
1 per material type
as required
AASHTO T99
Soil Density Testing for
ASTM D2922
50-100 ft. every lift and
Water, Sewer & Utility
AASHTO T2388/2239
39
at valves & manholes
95% compaction
Lines
one foot max
Soil Density Testing for
ASTM D2922/3017
50-100 ft. per lift
Structural Fill, Subbase,
AASHTO T238/239
max 12
o
95/o compaction
& Subgrade
Soil Density Testing for
ASTM D2922/3017
50-100 ft. per lift
3/4 -inch base
AASHTO T238/239
max 8"
95% compaction
Asphalt Rolling Pattern
n/a
as needed to controldensity
Depth & Density of AC
1 core per every 300
AASHTO T245
feet of standard road
0
95/o max unit weight
Cores
cross section
Rices
ASTM D2041
1 Rices per day
Oil Extraction
ASTM D4125 / NCAT
1 Extraction per day
Sieve Analysis
ASTM C136
1 Sieve per day
1 test per 50 cubic yds
Slump & Air Concrete
ASTM C143
(first test starts with
Per ISPWC
Control Tests
ASTM C231
first truck)
Concrete Compressive
per ISPWC Section 703
Per ISPWC Section 703
Per ISPWC Section 703
Strength Cylinders
81